Mounting
Installation and operating manual: PLATINUM Inverter 13000 TL, 16000 TL, 19000 TL, 22000 TL
Version 05/2010
Mat. No. 737 576-AB
For free-standing devices, the possibilities for cable routing through
Power Block protective housing TL Large are as follows:
Î
from front
Î
from below
Î
from back
Caution
Lack of performance and functionality due to
inappropriate cables!
Â
Ensure that wire cross sections and fuses conform to
VDE 100 Part 430.
Â
Ensure that any network cables between two
inverters are not longer than 30 m.
Â
Ensure that network cable of entire PV plant is not
longer than 1,000 m.
Â
For DC lines, use a wire cross section of at least
2.5 mm
2
.
Â
Ensure that admissible power dissipation of mains line
is not exceeded.
Caution
Material damage due to excessive voltage!
Â
Ensure that the max. DC voltage is not exceeded
(see 14 Technical Data).
Â
Connect exclusively safety extra low voltage on the
contact of the external indicator.