PLATINUM Inverter 13000 TL, 16000 TL, 19000 TL, 22000 TL
Start Up
Installation and operating manual: PLATINUM Inverter 13000 TL, 16000 TL, 19000 TL, 22000 TL
Version 05/2010
Mat. No. 737 576-AB
Note
The following screen is not displayed if only one inverter is started up.
Î
Entry only at one inverter. All inverters connected to the network
are blocked.
Î
With the number allocation completed, the inverter switches to
the
Country Code
screen.
Country code
In the menu
Country code
, the country where the inverter is operated
is set. Country-specific net conditions are set automatically in
dependence on the selected country.
Note
The setting can be changed within 4 hours after the setting and the
start of the feeding into the mains supply. Without feeding, the period
is prolonged. After the period has expired, the setting cannot be
changed anymore.
To select country code:
Â
Select desired country.
Â
Press OK key.
The inverter automatically transmits the country code setting to all
network participants.
Key
Function
ST
Select country.
OK
Accept selection.
PLATINUM Wechselrichter TL Large_GB.book Page 37 Thursday, September 2, 2010 4:13 PM