User manual - ATR902 - 23
23
AL. 1
Alarm 1
Alarm 1 selection.
Dis.
(Disabled). >
Default
.
a. aL.
(Absolute Alarm). referring to the process
b. aL.
(Band Alarm). Command sepoint ± band
u.d.aL.
(Upper Deviation Alarm). Command se deviation
L.d.aL.
(Lower Deviation Alarm). Command setpoint - deviation
a.c.S.L.
(Absolute Command Setpoint Alarm). Reff erring to the sepoint
St.AL.
(Start Alarm). Active in RUN
end.a.
(End Alarm). Active at cycle end
a.o.r.S.
(Auxiliary Output Related to the Step). ON/OFF at each step
a.o.r.m.
(Auxiliary Output Rising Maintenance). Auxiliary output active for
rising and holding steps
a.o.fa.
(Auxiliary Output Falling). Auxiliary output active for falling steps.
24
a.1.s.o.
Alarm 1 State Output
Selects contact type for alarm 1 output.
n.o.
(Normally Open). >
Default
n.c.
(Normally Closed).
25
a.1.tH.
Alarm 1 Threshold
Selects setpoint value for alarm 1.
-260…+3200 degrees. >
Default
: 0.
26
a.1.Hy.
Alarm 1 Hysteresis
Selects hysteresis for alarm 1.
-99.9…+99.9 tenths of degree. >
Default
: 1.0.
27
a.1.se.
Alarm 1 State Error
Contact satus for alarm 1 output in case of error
o.c.
(Open Contact) >
Default
c.c.
(Closed Contact)
28
a.1.Ld.
Alarm 1 Led
Defines the status ON of led
A1
in correspondence of the relevant contact.
o.c.
(Open Contact)
c.c.
(Closed Contact) >
Default