User manual - ATR 142
35
1101
Visualized Setpoint 1 (decimal as
display)
R/W EEPROM
1102
Visualized Setpoint 2 (decimal as
display)
R/W EEPROM
1103
Visualized Setpoint 3 (decimal as
display)
R/W EEPROM
1104
Visualized Setpoint 4 (decimal as
display)
R/W EEPROM
1105
Visualized Alarm 1 (decimal as
display)
R/W EEPROM
1106
Visualized Alarm 2 (decimal as
display)
R/W EEPROM
1107
Setpoint gradient (decimal as
display)
RO EEPROM
1108
Heating output percentage
(0-1000)
RO
0
1109
Heating output percentage (0-100)
RO
0
1110
Cooling output percentage
(0-1000)
RO
0
1111
Cooling output percentage (0-100)
RO
0
2001
Parameter 1
R/W EEPROM
...
...
...
...
2064 Parameter 64
R/W EEPROM
3000 Disabling serial control of
machine
**
WO
0
3001
First word display1 (ASCII)
R/W
0
*
If value is 0, the control is disabled. If different from 0, it is the max. time
which can elapse between two pollings before the controller goes off-
line. If it goes off-line, the controller returns to Stop mode, the control
output is disabled but the alarms are active.
**
By writing 1 on this word, the effects of the writing are cancelled on all
the Modbus addresses from 3001 to 3022. Control therefore returns to
the controller.