User manual - ATR 142
33
500
Loading default values:
9999
restore all values
9998
restore all values except for
baud-rate and slave address
9997
restore all values except for
slave address
9996
restore all values except for
baud-rate
WO
0
1000
Process (with tenths of degree for
temperature sensors; digits for
linear sensors)
RO
-
1001
Setpoint1
R/W EEPROM
1002
Setpoint2
R/W EEPROM
1003
Setpoint3
R/W EEPROM
1004
Setpoint4
R/W EEPROM
1005
Alarm1
R/W EEPROM
1006
Alarm2
R/W EEPROM
1007
Setpoint gradient
RO EEPROM
1008
Outputs status (0=off, 1=on)
Bit 0 =
Q1
relay
Bit 1 =
Q2
relay
Bit 2 =
SSR
RO
0
1009
Heating output percentage
(0-10000)
RO
0
1010
Cooling output percentage
(0-10000)
RO
0
1011
Alarms status (0=none, 1=active)
Bit0 = Alarm 1
Bit1 = Alarm 2
RO
0