ON Position
OFF Position
In MANUAL mode:
• The MC LCDs could be off or continue to display
whatever was showing at the time of switchover
from AUTO to MAN.
• To start the pump, no PIN CODE is required; the
pump will start as soon as the nozzle is taken off
its seat and will stop when the nozzle is put
back.
• The quantity dispensed by CUBE MC is not
indicated in any way.
To prime the pump:
- Take the nozzle off its seat
- Enter the previously assigned PIN CODE (if the jumper is on)
- Lift the control lever
- The pump will start immediately and will continue running indefinitely until the control lever
is moved to OFF position.
Operate the lever of the automatic nozzle, keeping the spout inside an adequate container or
the same suction tank.
Air will first of all come out of the nozzle and then DIESEL FUEL will gradually begin to flow.
I5
FIRST PRIMING
EN
16
(Translated from Italian)
The jumper is only accessible by opening the front panel and is positioned as shown in the
photo. In this operating mode, MC does not record any data relating to performed
dispensing operations.
BEFORE ACCESSING THIS JUMPER, ALWAYS INTERRUPT THE POWER SUPPLY
! ATTENTION
The first priming of the pump must be done by skilled personnel who must monitor all
the various stages involved.
If only air continues to come out after more than two minutes, STOP THE PUMP and
make sure:
! ATTENTION
Содержание cube mc
Страница 1: ...Bulletin M0104D EN Rev 1 CONSUMER PUMPS CONSUMER PUMPS ENGLISH USE AND MAINTENANCE MANUAL ...
Страница 2: ...2 EN ...
Страница 24: ...EN 24 CUBE MC SPARE PARTS O Translated from Italian ...
Страница 26: ...EN 26 NOTES ...
Страница 27: ...27 EN NOTES ...