Commissioning
Operating Manual PSENvip RL D P Set
1001641-EN-09
| 72
Evaluation of the "Out of range" message:
Note that the
Out of range
message is for information only.
The guide frame indicates the maximum possible protected field based on the press over-
run. The maximum possible protected field is needed in the event of a maximum overrun of
14 mm. If the tool centre point is at the lower end of the range bar in the event of a max-
Make adjustment during tool change [
) and the
Out of range
message appears, this can lead to false stops during operation. In this case you must cor-
rect the adjustment.
If you comply with the specifications for the required protected field size and the overrun is
less than 14 mm, the adjustment can also be completed when the
Out of range
message
appears.
Note the following specifications regarding the required protected field, based on the over-
run.
8 mm
10 mm
12 mm
14 mm
16 mm
18 mm
20 mm
44 mm
[1]
Fig.: Required protected field based on the overrun
Legend
[1]
Tool detection
Overrun
Height of the protected field
(O 6 mm)
Colour of protected field
(see diagram)
14 mm
20 mm
(maximum protected field)
White
12 mm
18 mm
Blue
10 mm
16 mm
Green
8 mm
14 mm
Yellow
6 mm
12 mm
Brown