Operation
Operating Manual PSEN sg2c
1003267EN02
45
Error code Description
Remedy
1
Short circuit on 0 V DC with at
least one of the two safety outputs
X13 and X14
Check the wiring of terminals X13 and
X14, rectify the wiring error
2
During operation, short circuit
between safety output X13 and 24
V DC
Rectify wiring error at terminal X13
3
During operation, short circuit
between safety output X14 and 24
V DC
Rectify wiring error at terminal X14
4
At least one of the two safety out
puts X13 and X14 have voltage
applied during system runup
Check the wiring of terminals X13 and
X14, rectify the wiring error