Function description
Operating Manual PSEN sg2c
1003267EN02
10
4
Function description
The interlocking and guard locking system prevents the safety gates to the danger zone
from opening while the hazardous machine is switched on.
There is a high signal (safety gate closed and locked) at safety outputs X13 and X14 if the
following conditions are met simultaneously:
}
Inputs X23 and X24 are high and
}
The bolt tongue is within the response range and
}
The guard locking element is engaged in the bolt tongue and
}
The escape or auxiliary release pin is in the correct position.
Signal output X19 is high if:
}
The bolt tongue is within the response rang
There is a low signal (safety gate open and hazardous machine function interlocked) at
safety outputs X13 and X14 if the following occurs:
}
Inputs X23 or X24 are low or
}
The guard locking element is outside the bolt tongue or
}
The escape or auxiliary release has been operated
If the safety outputs have been shut down by either of the inputs X23 or X24, they cannot
be switched back on until both inputs are low simultaneously.
A High signal has to be present at X16 (X26) and a Low signal at X17 (X27) for operat
ing the solenoid after the hazardous movement has been ended.
4.1
Normal /Unlock mode
Normal mode:
The safety gate to the danger zone is not unlocked until the hazardous machine is stopped
and the pushbutton for access request has been operated.
}
The guard locking element is disengaged from the bolt tongue as soon as there is a
high signal at terminals X16 and X17 or X26 and X27, followed by operation of the
pushbutton for access request.
Unlock mode:
The safety gate to the danger zone is unlocked when the hazardous machine is stopped.
This enables easier access for cleaning staff once the shift has ended, for example.
}
The guard locking element is disengaged from the bolt tongue as soon as there is a
high signal at terminals X16 and X17 or X26 and X27.