PMUT X1P
Operating Manual PMUT X1P
20587-EN-06
18
Semiconductor output
Y32: Light grid active
Y33: Muting active
Y34: Muting lamp warning
Y35: Both muting lamps defective
Y36: Safety contacts closed
Application example
13
23
33
14
24
34
A1
A2
S1+
S3+
S2+
S4+
S1
S3
S2
S4
S43 S44 Y1
S11 S12
S21
LA+ LA-
LB+ LB-
Y2
S33 S34
S32
S31
S22
PMUT X1P
OSSD1
OSSD2
S1
S3
S2
S4
+24 V DC
0 V
K5
K6
K5
K6
Operation
When the relay outputs are switched on, the mechanical contact on the relay cannot be
tested automatically. Depending on the operational environment, measures to detect the
non-opening of switching elements may be required under some circumstances.
When the product is used in accordance with the European Machinery Directive, a check
must be carried out to ensure that the safety contacts on the relay outputs open correctly.
Open the safety contacts (switch off output) and start the device again, so that the internal
diagnostics can check that the safety contacts open correctly
}
for SIL CL 3/PL e at least 1x per month
}
for SIL CL 2/PL d at least 1x per year