8.1
Operating states
8
Operation
8-2
8.1
Operatingstates
8100
Operatingstates
8-
Betrieb_Zustaende
Thesafetycardisalwaysinclearlydefinedoperatingstates.
POWERON
Thesupplyvoltagesarepresent.
TransitiontoSTOoncethesupplyvoltagesareapplied
CONFIG
Downloadofconfigurationtothesafetycard
TransitiontostateofNORMALOPERATION:Configurationdown-
loadedwithouterror
TransitiontostateofSTO:Incorrectconfigurationdata
ThemotorisswitchedvoltfreeintheCONFIGoperatingstate(STOis
active)
NORMALOPERATION
Nosafetyfunctionactivated
TransitiontostateofSTO:Internalerror
TransitiontoSAFEOPERATION:Asafetyfunctionisactivated
SAFEOPERATION
Safeoperationafteratleastonesafetyfunctionhasbeenactivated
TransitiontoSTO:Internalerror
TransitiontoSS1dueto
– Error
– Violationoflimitvalues
– DemanduponsafetyfunctionSS1
TransitiontoNORMALOPERATION:Nosafetyfunctionactivated
NORMAL
OPERATION
CONFIG
SAFE
OPERATION
SS1
STO
POWER ON
Download
configuration
Safety
function
deactivated
Safety
function
activated
Demand
upon
Configurator
Internal error
Error
STO
Limit values
Error
SS1 Activate
Error
Reset