phytron
15
MA 1263-A010 EN
8.1.2 Status Code (CPU)
Status (2 bytes)
Meaning
0001
H
Command error
0002
H
Range value error
0004
H
Checksum error (CRC)
0008
H
ADDR error (card could not be addressed)
0010
H
Timeout error on bus
0020
H
Bad value error
0040
H
Interface error (frame)
0080
H
Software error
0100
H
Internal program is running
0200
H
Forced switch over to remote via PC
1000
H
Programming error: internal program
2000
H
Flag ‚Parameters are changed‘;
this flag is reset by the command 0201
H.
4000
H
Input inquiry active (wait for input status)
8000
H
Remote/Local switch on Remote
8.1.3 Error Code (CPU)
Error (1 byte)
Meaning
00
H
OK
0m
H
Error in module no. m
m: module number 1 to 14
H
(module 1 to 20 in one sub rack)