10 |
Page
V1.0
Table 7 Input Wiring (75°C Wire)
Wire size recommendations based on 600VAC, 75°C rated copper wire. Assuming 86°F
(30°C) ambient and no more than 3 current carrying conductors in raceway, cable or earth
(directly buried).
Input Wiring Recommendations
Heavy Duty
1
Light Duty
2
Circuit
Breaker
Wire Gauge
Torque
in-lb
Circuit
Breaker
Wire
Gauge
PT007
60
6 AWG
120
50
8 AWG
PT010
80
4 AWG
120
60
6 AWG
PT020
150
1/0 AWG
120
125
1 AWG
PT030
200
3/0 AWG
275
200
3/0 AWG
PT040
250
250 kcmil
275
250
250 kcmil
PT050
400
2x3/0
375
300
350 kcmil
PT060
500
2x250 kcmil
375
350
500 kcmil
PT075
600
2x350 kcmil
375
500
2x4/0 AWG
PT407
30
10 AWG
120
30
10 AWG
PT410
40
8 AWG
120
40
8 AWG
PT415
60
6 AWG
120
50
8 AWG
PT420
70
4 AWG
120
60
6 AWG
PT430
100
3 AWG
120
100
3 AWG
PT440
150
1/0 AWG
120
125
1 AWG
PT450
175
2/0 AWG
120
150
1/0 AWG
PT460
200
3/0 AWG
275
200
3/0 AWG
PT475
250
250 kcmil
275
250
250 kcmil
PT4100
400
2x3/0
375
300
350 kcmil
1
Heavy Duty: Single motor loads with heavier inertial loads that typically require class 10
overload.
2
Light Duty: Non motor loads, system not running near full load amps, motors that start
with little or no inertial load, motors started with a soft starter.
NOTE: PT060 & PT075 are not rated to start across the line motors at the full horsepower
rating.