Grounding
Properly ground the phase converter according to local electrical code.
Connect the ground lug to the branch circuit or service ground conductor.
Ground the phase converter with an adequately sized conductor according to
local electrical code.
Table 6 Ground Wire Specifications
Torque specifications based on solid to semi-rigid stranded copper wire. See terminal
markings for additional wire size and torque information.
Wire Range
(AWG)
Min Wire Size w/specified
Breaker
Models
Min
Max
Breaker
(A)
Wire
AWG
Torque
(in-lb)
PT007
14
2
60
10
40
PT010
14
2
80
8
40
PT020
14
2
150
6
40
PT030
14
2
200
6
40
PT040
14
2
250
4
50
PT050
14
2/0
400
3
50
PT060
14
2/0
500
2
50
PT075
14
2/0
600
1
50
PT407
14
2
30
10
40
PT410
14
2
40
10
40
PT415
14
2
60
10
40
PT420
14
2
70
8
40
PT430
14
2
100
8
40
PT440
14
2
150
6
40
PT450
14
2
175
6
40
PT460
14
2
200
6
40
PT475
14
2
250
4
50
PT4100
14
2/0
400
3
50