16 |
Page
V1.0
ON/OFF Control Wiring
The output of the converter can be controlled with a low power switch connected between
the AUX1 or AUX2 and COM terminals. If installed, remove the factory installed jumper
wire and replace with a switch. See
Figure 17
.
When AUX1 to COM or AUX2 to COM is closed, the output is energized after a delay of
approximately two seconds. When AUX1 and AUX2 to COM are open, the output of the
converter will be de-energized.
The diagram in
Figure 13
illustrates the UL508A panel shop and customer installed options
including an ON/OFF control switch
.
Figure 13
– Panel Shop Options
WARNING!
When the converter is turned OFF using a switch on the AUX terminals,
dangerous voltage may still be present on the input lines and elsewhere inside the
enclosure.
Never open the enclosure or perform maintenance on the unit or connected
loads when the low power remote switch is in the ON position.