INSTALLATION
Mounting Your New Phase Perfect
Proper installation of the unit
is important to the performance and normal operating life of
the unit. The unit should be installed in a location free from:
Corrosive gases or liquids
Excessive vibration
Airborne metallic particles
Mount the unit to a solid, non-flammable surface capable of bearing the weight using the
mounting brackets provided with the unit. Weights for each model can be found in
Mounting Bracket Installation
For shipping purposes, mounting brackets may be installed upside down. If the mounting
brackets are not installed in an upright position, remove the mounting screws and turn to an
upright position, then fasten the screws tightly.
Proper Ventilation
In order to maintain air circulation for adequate cooling, minimum clearance around the unit
must be maintained. Allow six inches on each side and top, and 18 inches below.
Ensure air intake and exhaust openings are not obstructed. If the unit is mounted in a small
room, cabinet, or building, ensure there is adequate ventilation to provide sufficient cooling
for the unit.
Service Entrance Equipment
The Phase Perfect phase converters are suitable for use as service equipment when the
molded case circuit breaker (MCCB)/disconnect, service ground conductor terminal and
grounding electrode conductor are factory installed and the converter is labeled “Suitable
for use as Service Equipment.” Consult local electrical code for installation guidance.
Source Branch Circuit Protection
If a circuit breaker is not factory installed, branch circuit protection must be installed in the
circuit sourcing the phase converter. See
for recommended circuit breaker sizing.
Fuses may be used for circuit protection, consult local electrical code for proper sizing.
Installation of a disconnection means within sight of the phase converter is recommended.