Table 8 Input Wiring (60°C Wire)
Wire size recommendations based on 600VAC, 60°C rated copper wire. Assuming 86°F
(30°C) ambient and no more than 3 current carrying conductors in raceway, cable or earth
(directly buried).
Input Wiring Recommendations (60°C rated wire)
Heavy Duty
Light Duty
240 V
Circuit
Breaker
(A)
Wire
Gauge
Torque in-lb
Circuit
Breaker
(A)
Wire
Gauge
PT007
60
4 AWG
120
50
8 AWG
PT010
80
3 AWG
120
60
6 AWG
PT407
30
10 AWG
120
30
10 AWG
PT410
40
8 AWG
120
40
8 AWG
PT415
60
4 AWG
120
50
6 AWG
PT420
70
4 AWG
120
60
4 AWG
PT430
100
1 AWG
120
100
1 AWG
Wire Sizing
Use
to find minimum guidelines in properly sizing input and output conductors
according to local electrical code. The voltage drop from the supply to the converter should
be limited to 3% to ensure proper starting and operation of motor loads. Increase the wire
gauge to provide adequate voltage to the load. Ensure the wire gauge is suitable to the
terminal block.
Use the following formula to calculate line voltage drop.
𝑉
𝑑𝑟𝑜𝑝
= 𝑤𝑖𝑟𝑒 𝑟𝑒𝑠𝑖𝑠𝑡𝑎𝑛𝑐𝑒 (
Ω
𝑓𝑡
) 𝑋 𝑤𝑖𝑟𝑒 𝑙𝑒𝑛𝑔𝑡ℎ (𝑓𝑡) 𝑋 𝑐𝑢𝑟𝑟𝑒𝑛𝑡
Connecting the Load
Do not connect single phase loads to the manufactured leg, T3. This places unnecessary
load on the phase converter and may violate electrical code in some areas. Apply overload
and short circuit protection to protect load side conductors, motors and other attached
loads according to local electrical code. For some motor loads and wiring configurations
load side short circuit protection may not be required. Consult local electrical code for
guidance.