5-16

RPS Series: Remote Power Switches - User's Guide

5.3.4.  Network Parameters Menus

The Network Parameters Menus are used to select the IP Address and other 

network parameters.

• 

Web Browser Interface:

  Click the "Setup" button to access the Setup 

Menus, and then click the "Network Parameters" button.  The Web 

Parameters Menu will be displayed as shown in Figure 5.9.

• 

Text Interface:

  Type 

/N

 and press 

[Enter]

.  The Network Parameters 

Menu will be displayed as shown in Figure 5.10.

Notes:

•  Although the Web Browser Interface and Text Interface both 

allow configuration of the same network parameters, note that 

for the Text Interface, the IP Security feature is configured via a 

separate submenu.  For more information on IP Security, please 

refer to Section 5.3.4.1.

•  Settings for network parameters depend on the configuration of 

your individual network.  Contact your network administrator 

for appropriate settings.

The Network Parameters Menu allows the following parameters to be defined.  

Except where noted, all parameters listed here are available via both the Web 

Browser Interface and the Text Interface.

• 

IP Address:

  Defines the IP address for the RPS unit.   

(Default = 192.168.168.168.)

• 

Subnet Mask:

  Defines the Subnet Mask for the RPS unit.   

(Default = 255.255.255.0.)

• 

Gateway Address:

  Defines the Gateway Address for the RPS unit.   

(Default = undefined.)

• 

Send MSS:

  Defines the Maximum Segment Size that will be sent by the 

RPS.  (Default = 536.)

• 

IP Security:

  Please refer to Section 5.3.4.1 for a detailed description of 

the IP Security feature.

• 

MAC Address:

  Displays the unit’s MAC Address.  Please note that this 

item only displays the assigned MAC Address, and cannot be used to 

redefine the address.

Notes:

•  To display the Network Status Screen, type 

/SN

 and press 

[Enter]

.

•  To reset the Network Port, type 

/R

 and press 

[Enter]

.

Содержание RPS1620

Страница 1: ...5500193 10 RPS Series RemotePowerSwitches Models Covered RPS820 RPS830 RPS1620 RPS1630 User s Guide ...

Страница 2: ......

Страница 3: ...nt protection and supply wiring GROUNDING Reliable earthing of this equipment must be maintained Particular attention should be given to supply connections when connecting to power strips rather than direct connections to the branch circuit No Serviceable Parts Inside Authorized Service Personnel Only Do not attempt to repair or service this device yourself Internal components must be serviced by ...

Страница 4: ...to an outlet on a circuit that is different from the one used by the receiver Consult the dealer or an experienced radio TV technician for help This device complies with Part 15 of the FCC rules Operation of this device is subject to the following conditions 1 This device may not cause harmful interference and 2 this device must accept any interference that may cause undesired operation WARNING Ch...

Страница 5: ...Interface 5 3 5 2 2 Accessing the Text Interface 5 4 5 3 Configuration Menus 5 6 5 3 1 The General Parameters Menus 5 6 5 3 2 The Serial Parameters Menu 5 10 5 3 3 The Plug Parameters Menus 5 12 5 3 3 1 Plug Passwords and Co Location Features 5 14 5 3 3 2 The Boot Sequence Delay Period 5 15 5 3 4 Network Parameters Menus 5 16 5 3 4 1 IP Security Feature 5 18 5 3 5 The Telnet Parameters Menus 5 20 5...

Страница 6: ...face Model RPS830 Shown 3 4 5 1 Plug Status Screen Web Browser Interface Model RPS830 Shown 5 2 5 2 Plug Status Screen Text Interface Model RPS830 Shown 5 4 5 3 General Parameters Menu Web Browser Interface 5 7 5 4 General Parameters Menu Text Interface 5 7 5 5 Serial Parameters Menu Web Browser Interface 5 10 5 6 Serial Parameters Menu Text Interface 5 10 5 7 Plug Parameters Menu Web Browser Inte...

Страница 7: ...communicate over any TCP IP network using standard Telnet or out of band using an external modem and basic VT100 type terminal emulation Security Features and Co Location Features To ensure security web browser access requires the user to enter an assigned user name and password The RPS provides two levels of operational passwords the System Administrator Level which allows access to all configurat...

Страница 8: ... One 1 Rack Unit RPS830 Horizontal mount Eight 8 switched 100 to 120 VAC NEMA 5 15R outlets 30 Amps maximum total load One 1 Rack Unit RPS1620 Vertical mount Sixteen 16 switched 208 to 240 VAC IEC 320 C13 outlets 20 Amps maximum total load Zero 0 Rack Unit RPS1630 Vertical mount Sixteen 16 switched 100 to 120 VAC NEMA 5 15R outlets 30 Amps maximum total load Zero 0 Rack Unit Typographic Convention...

Страница 9: ... Panel Model RPS830 Shown 2 2 RPS820 and RPS830 Back Panel As shown in Figure 2 1 the back panels for RPS820 and RPS830 models include the following components Bus A Power Inlet and Circuit Breaker An IEC 320 C14 AC inlet and circuit breaker which supply power to the Circuit A outlets outlets one through four Also includes cable keeper not shown RPS820 208 240 VAC Power Inlet 10 Amp Circuit Breake...

Страница 10: ...ed parameters will be reset to default values Manual Plug Toggle Press the Default Button and hold it down for three seconds All RPS power outlets will be toggled On or Off Note If desired the Default Button s manual plug control capabilities can also be disabled as described in Section 5 3 1 Unit Status Indicators Two LED Indicators which function as follows ON Lights when power is applied to the...

Страница 11: ...ower outlets LEDs and a manual control button The items in Figure 2 2 are described on the following page PLUGS READY ACTIVITY 10BaseT RS232 CONSOLE DTE PLUG 1 PLUG 2 PLUG 3 PLUG 14 PLUG 15 PLUG 16 PWR CKT A PWR CKT B Remote Power Switch 1 2 3 4 5 6 7 8 9 Figure 2 2 RPS1620 and RPS1630 Hardware Model RPS1630 Shown ...

Страница 12: ...ur TCP IP network The default IP Address is 192 168 168 168 for more information please refer to Section 5 3 4 RS232 Console Port A DB9 RS232 serial port DTE for connection to a local terminal or external modem as described in Section 4 3 Master Power Switch This switch must be On in order for the RPS to function Note that this switch is not used to set the On Off status of the switched outlets Sw...

Страница 13: ...er Inlet Two 2 208 to 240 VAC IEC 320 C14 AC inlets Circuit Breaker 10 Amps Model RPS1630 Power Inlets Two 2 100 to 120 VAC IEC 320 C14 AC inlets Circuit Breaker 15 Amps Power Circuit B Input Components An AC Inlet and circuit breaker which supply power to plugs 9 through 16 Includes same components as Circuit A Rack Mounting Brackets Not Shown ...

Страница 14: ...2 6 RPS Series Remote Power Switches User s Guide ...

Страница 15: ...0 and RPS1630 units should be connected to a 100 to 120 VAC power supply and RPS820 and RPS1620 units should be connected to a 208 to 240 VAC power supply CAUTION Make certain to review the safety precautions listed in Section 4 1 and at the beginning of this User s Guide Note that RPS units feature two separate AC inputs Connect power supply cables to the RPS s Circuit A and Circuit B inlets and ...

Страница 16: ...s follows 9600 bps 8 Data Bits One Stop Bit No Parity Although the RPS allows these parameters to be easily redefined for the purpose of this Quick Start procedure it is recommended that you configure your communications program to accept these default parameters 3 2 Communicating with the RPS The RPS offers two separate user interfaces the Web Browser Interface and the Text Interface The Web Browse...

Страница 17: ...wn in Figure 3 1 b Text Interface i Via Telnet Telnet to the RPS s default IP address 192 168 168 168 The Plug Status Screen Figure 3 2 should be displayed ii Via Local PC Start your communications program e g Hyperterminal and then press Enter The Plug Status Screen should be displayed as shown in Figure 3 2 The default communications parameters for the Console Port are 9600 bps No Parity 8 data ...

Страница 18: ...tatus Boot Seq Delay Default 1 undefined undefined ON 0 5 Secs ON 2 undefined undefined ON 0 5 Secs ON 3 undefined undefined ON 0 5 Secs ON 4 undefined undefined ON 0 5 Secs ON 5 undefined undefined ON 0 5 Secs ON 6 undefined undefined ON 0 5 Secs ON 7 undefined undefined ON 0 5 Secs ON 8 undefined undefined ON 0 5 Secs ON H for help RPS Figure 3 2 Plug Status Screen Text Interface Model RPS830 Shown ...

Страница 19: ...er Interface select the button in the On column for Plug 1 and then click Apply From the Text Interface type ON 1 and press Enter The status indicator for Plug 1 should then go back On indicating that the command has been successfully completed 3 Log Out When you have finished communicating with the unit it is important to always log off by issuing the appropriate RPS command rather than simply clo...

Страница 20: ...3 6 RPS Series Remote Power Switches User s Guide ...

Страница 21: ...Phillips head screws to secure each cable keeper to the unit make certain the cables are secure and then connect the cables to an appropriate power supply RPS830 and RPS1630 units should be connected to a 100 to 120 VAC Power Supply and RPS820 and RPS1620 units should be connected to a 208 to 240 VAC power supply Set the RPS s Master Power Switch in the On position The Master Power Switch must be ...

Страница 22: ...r wired in a DTE configuration similar to an AT computer In the default state the Console port is configured for 9600 bps no parity 8 data bits 1 stop bit The Console Port can be connected to either an external modem or a local PC but not both items at the same time Appendix A describes the Console Port interface 4 3 1 Connecting a Local PC When connecting the Console Port to a Local PC note that th...

Страница 23: ...ent it is recommended to define network parameters as described in Section 5 3 4 Note The RPS features a 10Base T Interface When connecting to a 100Base T interface most router switches will autosense to determine if the device is 100Base T or 10Base T and then configure the network interface accordingly If your router switch does not autosense the network interface port must be manually set to 10Ba...

Страница 24: ...4 4 RPS Series Remote Power Switches User s Guide ...

Страница 25: ... Mode or User Mode If the System Password is entered the System Mode will be active If a Plug Password is entered the User Mode will be active The System Password is defined via the General Parameters menu Section 5 3 1 and the Plug Passwords are defined via the Plug Parameters Menu Section 5 3 3 Notes If you wish to restrict access to configuration menus you must define the System Password If the Sys...

Страница 26: ...three different methods for accessing command mode via network via external modem or via local console The Web Browser Interface is only available when the RPS is contacted via network and the Text Interface is available via network modem or local PC The sections that follow describe the procedure for accessing the Web Browser Interface or the Text Interface Note Configuration functions are only av...

Страница 27: ...d then press Enter 3 Password Prompt The RPS will display a prompt which asks for your name and password a User Name If you have not previously defined a user name then this field should be left blank A user name is only required when one has been defined via the General Parameters menu b Password Key in your System Password or Plug Password and then click OK Note that Plug Passwords do not permit ac...

Страница 28: ...e must be connected to the external modem Your PC Must include a communications program Access Via Local PC Your local PC Must be connected to the RPS s Console Port The local PC must include a communications program Remote Power Switch v1 43s Site ID undefined Plug Name Password Status Boot Seq Delay Default 1 undefined undefined ON 0 5 Secs ON 2 undefined undefined ON 0 5 Secs ON 3 undefined undefined ...

Страница 29: ...et to the RPS s IP address For example if the IP address is 192 168 168 168 then on a UNIX system the Telnet command would be telnet 192 168 168 168 Enter ii If the Telnet connection is refused this may mean that either the IP Security feature has denied the connection See Section 5 3 4 1 or that unit is operating on a 100Base T network that does not autosense for 10Base T devices see Section 4 4 ...

Страница 30: ... the desired menu When the configuration menu appears key in the number or letter for the parameter that you wish to define and follow the instructions in the resulting submenu Note the following To exit from a parameters menu press the Esc key The following sections describe the options and parameters that can be accessed via each of the configuration menus Please note that essentially the same sele...

Страница 31: ...RS 1 System Password undefined 2 User Name undefined 3 Site ID undefined 4 Command Echo On 5 Inactivity Timeout 2 Mins 6 Command Confirmation On 7 Automated Mode Off 8 Manual Switch Button On A Default Parameters Enter Selection Press ESC to Exit Figure 5 4 General Parameters Menu Text Interface ...

Страница 32: ...ote that the User Name is only required when the unit is accessed via the Web Interface 16 Characters Default undefined Notes If a User Name is defined then users who log in with a Plug Password User Mode will also need to enter this same User Name at the login prompt when attempting to access command mode via the Web Browser Interface The User Name cannot begin with a forward slash or backslash cha...

Страница 33: ... When this option is enabled security functions are suppressed and users are able to access System Level menus and control plugs without entering a password If security is a concern and the Automated Mode is required it is recommended to use the IP Security feature Section 5 3 4 1 to restrict access Manual Switch Button Enables and configures the manual plug control button Default On Off Disables t...

Страница 34: ...e Setup button to access the Setup Menus and then click the Serial Parameters button The Serial Parameters Menu will be displayed as shown in Figure 5 5 Text Interface Type C and press Enter The Serial Parameters Menu will be displayed as shown in Figure 5 6 Figure 5 5 Serial Parameters Menu Web Browser Interface SERIAL PARAMETERS 1 Baud Rate 9600 2 Data 8 Bit 3 Parity None 4 Stop 1 Bit 5 Port Mod...

Страница 35: ... Port Default 1 Bit Serial Port Mode Sets up the RPS Console Port for use with either a local PC Console or an external modem Modem Note that when the Serial Port Mode is set to Modem the modem initialization string will be sent every 15 minutes Default Console Modem Initialization String Defines a command string up to 32 characters long which can be sent out the serial Console Port to initialize a...

Страница 36: ...enus then click the Plug Parameters button The Plug Parameters Menu will be displayed as shown in Figure 5 7 Text Interface Type P n and then press Enter Where n is the number or name of the plug you wish to configure The Plug Parameters Menu will be displayed as shown in Figure 5 8 Figure 5 7 Plug Parameters Menu Web Browser Interface PLUG 3 PARAMETERS 1 Plug Name undefined 2 Password undefined 3 Bo...

Страница 37: ... this password does not allow access to configuration functions 16 Characters Default undefined Note Passwords cannot contain nonprintable characters spaces colons plus signs or quotation marks Boot Seq Delay When more than one plug is switched On Off or a reboot cycle is initiated the Boot Sequence delay determines how much time will elapse between switching operations as described in Section 5 3 3...

Страница 38: ...to issue switching and reboot commands for the corresponding plug and every other plug that shares this same password For example if the plug password switch is defined for plugs 1 2 and three then if a user logs into command mode using the password switch that user will be allowed to issue switching and reboot commands to plugs 1 2 and 3 but not plugs 4 through 16 Note that the Plug Passwords do n...

Страница 39: ...ume that the Boot Sequence Delays for each plug have been set as follows Plug 1 1 Second Plug 2 2 Seconds Plug 3 5 Seconds Plug 4 1 Minute Plug 5 1 Second If an On command is applied to the first five plugs the RPS will respond as follows 1 Turn On Plug 1 Wait 1 Second 2 Turn On Plug 2 Wait 2 Seconds 3 Turn On Plug 3 Wait 5 Seconds 4 Turn On Plug 4 Wait 1 Minute 5 Turn On Plug 5 If a Reboot Command ...

Страница 40: ...pend on the configuration of your individual network Contact your network administrator for appropriate settings The Network Parameters Menu allows the following parameters to be defined Except where noted all parameters listed here are available via both the Web Browser Interface and the Text Interface IPAddress Defines the IP address for the RPS unit Default 192 168 168 168 Subnet Mask Defines the S...

Страница 41: ...r Interface NETWORK PARAMETERS 1 IP Address 207 212 30 80 2 Subnet Mask 255 255 255 0 3 Gateway Address 207 212 30 1 4 Send MSS 536 5 IP Security MAC Address 00 09 9b 00 90 e0 Enter Selection Press ESC to Exit Figure 5 10 Network Parameters Menu Text Interface ...

Страница 42: ...Access the IP Security Menu a Web Browser Interface The IP Security feature is configured using the fields at the bottom of the Network Parameters Menu as shown in Figure 5 9 b Text Interface Go to the Network Parameters menu N type 5 and press Enter The IP Security menu will be displayed as shown in Figure 5 11 2 The IP Security menu lists five IP Security masks along with the selected permit deny a...

Страница 43: ...nly by addresses that begin with 192 deny access to 192 1 1 5 Security Mask 1 255 255 255 255 Mask 1 Action Deny Security Mask 2 192 255 255 255 Mask 2 Action Permit Security Mask 3 192 1 1 5 Mask 3 Action Deny Since 255 is a wild card Mask 1 blocks all IP addresses Mask 2 then grants access to all addresses that begin with 192 Finally Mask 3 specifically blocks access by 192 1 1 5 Note Mask 5 has ...

Страница 44: ...Interface 5 3 5 The Telnet Parameters Menus The Telnet Parameters Menus are used to enable disable Telnet access to the RPS command mode and select the TCP port for Telnet connections Web Browser Interface Click the Setup button to access the configuration menus and then click the Telnet Parameters button to display the menu shown in Figure 5 12 Text Interface Type T and press Enter The Telnet Para...

Страница 45: ...ables Telnet communication with the RPS unit When this item is set to the Off condition user s will not be able to contact the unit via Telnet Default On Port Number Selects the TCP IP port number that will be used for Telnet connections Default 23 Multiple Telnet When enabled allows up to four simultaneous Telnet connections to the RPS unit When disabled only one Telnet user may connect to the RP...

Страница 46: ...ers Menus The Web Server Parameters Menus are used to configure the RPS s internal web server which allows the unit to be operated via the Web Browser Interface Web Browser Interface Click the Setup button to access the configuration menus and then click the Web Server Parameters button The Web Server Parameters Menu will be displayed as shown in Figure 5 14 Text Interface Type W and press Enter The...

Страница 47: ...mpt you to save parameters before exiting from Command Mode At this point the RPS offers the options to Save parameters continue without saving or revert to the previously saved parameters Saving Parameters to an ASCII file allows you to create a backup of your currently defined configuration As described in Section 7 this provides quick recovery in the event that the unit is accidentally reset to de...

Страница 48: ...5 24 RPS Series Remote Power Switches User s Guide ...

Страница 49: ... The Plug Status Screen Figure 6 1 lists the current On Off status of the RPS s Switched Outlets and provides a series of radio buttons which are used to control switching and rebooting of the outlets To invoke switching and reboot commands or view plug status via the Web Browser Interface proceed as follows 1 Access the RPS Command Mode as described in Section 5 2 1 2 When the Plug Status Screen ...

Страница 50: ... To set all plugs to their user defined Power Up Default On Off status click the Default button in the All Plugs row and then click Apply Note that in order for this command to function Power Up Default values for each plug must first be defined as described in Section 5 3 3 When each switching reboot or default command is invoked the RPS will display a screen which indicates that a switching operati...

Страница 51: ...current status of the RPS s Switched AC Outlets and displays the firmware version and currently defined Site I D Message Normally the Plug Status Screen will also be redisplayed each time a command is successfully executed Note however that if desired the Automated Mode See Section 6 4 can be enabled to suppress the display of the Plug Status Screen after each command Remote Power Switch v1 43s Site...

Страница 52: ...r commands are successfully completed When switching or reboot operations are initiated Boot Sequence Delay times will be applied as described in Section 5 3 3 2 Remote Power Switch v1 43s Site ID undefined Display Configuration H Display Help Screen G View Set General Parameters S Display Plug Status P n View Set Plug Parameters SN Display Network Status C View Set Serial Parameters N View Set Netw...

Страница 53: ...lug Note that the BOOT command can also be entered as BO For example BOOT 1 or BO ATMSWTCH 4 Set Plugs to Power Up Defaults Type D and press Enter Plugs will be set to their default On Off status Power Up Default which is defined sing the Plug Parameters Menu as described in Section 5 3 3 Notes When you have accessed command mode using the System Password the Default command will be applied to all ...

Страница 54: ...e password that was used to access command mode 1 Several Plugs To apply a switching or reboot command to several plugs enter the numbers or names for the plugs separated by a plus sign For example to switch plugs 1 4 and 5 Off enter the following OFF 1 4 5 Enter 2 Series of Plugs To apply a command to a series of RPS Plugs enter the number for the plugs that mark the beginning and end of the seri...

Страница 55: ...wer switching functions without human intervention When the Automated Mode is enabled the ON OFF BOOT D and X commands are executed without a Sure confirmation prompt and without command response messages the only reply to these commands is the RPS prompt which is displayed when the command is complete Note that although the Automated Mode can be enabled using either the Web Browser Interface or Te...

Страница 56: ...e Prompt Suppressed All commands are executed without prompting for user confirmation 4 Error Messages Suppressed If the Enter key is pressed without entering a command the RPS will not respond with the Invalid Command message Note however that an error message will still be generated if commands are invoked using invalid formats or arguments All other status display and configuration commands will ...

Страница 57: ...c which allows downloading of ASCII files Note Although this function is available only via the Text Interface parameters that have been defined via the Web Browser Interface will also be sent to the ASCII file 7 1 Sending Parameters to a File 1 Start your communications program and access the RPS command mode using the System Level Password 2 When the RPS command prompt appears type DL and press Ent...

Страница 58: ...load an ASCII text file 4 Upload the file with the saved parameters If necessary key in the file name and directory path 5 When the upload is complete make certain to terminate the communications program s upload mode Note The current On Off status of each RPS plug will not be saved or restored However the selected default On Off setting for each plug will be saved and restored When the configuration ...

Страница 59: ... 7 before beginning this upgrade procedure 1 Obtain the update file Firmware modifications can either be mailed to the customer on a CDR or downloaded Place the upgrade CDR in your disk drive or copy the file to your hard drive 2 Access the RPS command mode via the Text Interface When the password prompt is displayed key in the System Level Password 3 When the command prompt appears type U and press ...

Страница 60: ...ate 6 Incomplete Upload If the upload is interrupted times out or if the update file becomes corrupted during transfer the RPS will display a screen which asks for confirmation before proceeding To proceed type 1 and press Enter then return to Step 4 above to retry the upload or press Esc to reboot the RPS unit 7 Recovery Mode In the rare event that the RPS operating system becomes corrupted during ...

Страница 61: ...Apx 1 A Interface Descriptions A 1 Console Port Interface Figure A 1 Console Port Interface ...

Страница 62: ...ets Split into Two 15 Amp Circuits Load 15 Amps per Circuit providing a Maximum Total of 30 Amps Model RPS1620 208 to 240 VAC AC Input Two Separate Circuits 10 Amps Maximum per Circuit Voltage 208 240 VAC 50 60 Hz Connectors Two 2 IEC 320 C14 Inlets AC Outputs Connectors Sixteen 16 IEC 320 C13 Outlets Split into Two 10 Amp Circuits Load 10 Amps per Circuit providing a Maximum Total of 20 Amps Mode...

Страница 63: ...cm 1 Rack U Models RPS1620 and RPS1630 Vertical Mount Width 1 75 4 5 cm Depth 3 00 7 6 cm Length 43 75 111 1 cm Weight Model RPS820 8 lbs 3 6 Kg Shipping Weight Model RPS830 9 lbs 4 1 Kg Shipping Weight Models RPS1620 10 lbs 4 5 Kg Shipping Weight Model RPS1630 11 lbs 5 Kg Shipping Weight Temperature Operating 32 F to 122 F 0 C to 50 C Humidity 10 90 RH ...

Страница 64: ...eded when making a query on page Apx 6 Making a support query via the Perle web page on page Apx 7 C 2 Who to Contact If you bought your product from a registered Perle supplier you must contact their Technical Support department they are qualified to deal with your problem If you are a registered Perle supplier and bought your product from Perle contact Perle Technical Support at the offices listed...

Страница 65: ...our technical support teams by email using the addresses shown in the next table Region Address Email North America Perle Systems Ltd 60 Renfrew Drive Markham Ontario Canada L3R OE1 Email ptac perle com Europe Perle Systems Europe Ltd 3 Wintersells Road Byfleet Surrey KT14 7LF UK Email ptac perle com Asia Perle Asia Pacific Pte Ltd Yu Li Industrial Building No 37 Lor 23 Sims Avenue 04 01 05 Singapor...

Страница 66: ...lowing information ready Hint Print out this page and fill in the table provided with the basic information you need Item Write details here Product name and version Problem description Operating system version Driver version Details of any other cards installed in your system Your name Company Name Country Phone number Fax number Email address if available ...

Страница 67: ...tact details for the Perle technical support centres C 5 Repair procedure Before sending a unit for repair you must contact your Perle supplier If however you bought your product directly from Perle you can contact directly See Perle support centres worldwide on page Apx 5 for contact information Customers who are In Europe Africa or Middle East can submit repair details via a website form This fo...

Страница 68: ...ts to improve reliability function or design Microsoft and Internet Explorer are trademarks of Microsoft Corporation Netscape is a trademark of Netscape Communications Corporation ProComm is a registered trademark of DATASTORM TECHNOLOGIES INC Crosstalk is a registered trademark of Digital Communications Associates Inc VT100 is a trademark of Digital Equipment Corporation AT is a registered tradem...

Страница 69: ... Confirmation Prompt 5 9 Console Port 4 2 5 11 Apx 1 Baud Rate 5 11 Data Bits 5 11 Parity 5 11 RPS1620 and RPS1630 2 4 RPS820 and RPS830 2 2 Stop Bits 5 11 D Data Bits 5 11 Default Button RPS820 and RPS830 2 2 Default On Off 5 13 Default Parameters 5 9 Delay Period 5 15 Deny Access 5 18 Disable Telnet 5 20 to 5 21 Downloading Parameters 7 1 Duplex Mode 5 8 E Error Messages 6 8 Ethernet Port 4 3 Ext...

Страница 70: ...9 Plug Indicators RPS1620 and RPS1630 2 4 RPS820 and RPS830 2 2 Plug Name 5 13 Plug Parameters Menu 5 12 to 5 14 Plug Password 5 13 Plug Status Screen 6 8 Text Interface 6 3 Web Browser Interface 6 1 Port Number Telnet 5 21 Web Server 5 23 Power Control Manual 6 8 Text Interface 6 3 to 6 5 Web Browser Interface 6 1 to 6 3 Power Indicator RPS820 and RPS830 2 1 Power Inlets RPS1620 and RPS1630 2 5 R...

Страница 71: ...Disable 5 20 to 5 21 Port Number 5 21 Service 5 21 Telnet Parameters Menu 5 20 Text Interface 5 4 to 5 5 6 3 to 6 5 Timeout 5 9 U Upgrade Firmware 8 1 to 8 2 Uploading Parameters 7 2 User Mode 5 1 5 14 User Name 5 3 5 8 User Password 5 13 W Warnings and Cautions i Web Browser Interface 5 3 to 5 4 6 1 to 6 3 Web Server Port Number 5 23 Service 5 23 Web Server Parameters Menu 5 22 to 5 23 Wild Card ...

Страница 72: ...Index 4 RPS Series Remote Power Switches User s Guide ...

Отзывы: