Operation and maintenance manual for the AGRO Multi series boilers with feeders. The producer reserves the right to introduce technical modifications.
4.4. Refuelling
The container should be refuelled regularly to maintain continu-
ous operation of the boiler. Fuel should be added when his layer
in the container reaches height min. 30 cm from the bottom of
the container - at the latest. Smoke and dust may be emitted
from the container in case of too low fuel amounts. If there is
no fuel the controller will shutdown whole system and it will be
necessary to
fi
re up a boiler. To refuel:
1. Turn o
ff
the fan.
2. The open
fl
ap of the fuel container.
3. Add fuel to the container.
4. Make sure that there are no contaminants, which can lock
operation of the feeder (debris, rocks, parts of wood metal).
5. The close tightly
fl
ap of the container.
6. Switch on the fan.
NOTE! During operation of the boiler fuel container should
be always tightly closed!
4.5. Stop of boiler operation
1. Switch to manual mode.
2. Turn o
ff
the fan and feeder.
3. Switch on the fuel feeder in manual mode for several min-
utes, taking a considerable amount of fuel out, to remove
whole heat from the burner.
4. Switch o
ff
controller.
5. Close tightly all doors,
fl
aps, damper on
fl
ue to damp the
system.
6. After dozen or so minutes check whether the fuel has not
reignited.
7. Remove remaining fuel from the container and feeder.
4.6. Boiler shutdown when the heating season is
fi
nished
To shutdown the boiler after the heating season you should
repeat operations listed in the
Stop of boiler operation
and then:
1. Remove fuel from container and feeder.
2. The clean whole boiler from inside,
fl
ue gas ducts and
chimney.
3. Leave open doors and lifted the cover of fuel container dur-
ing standstill of the boiler to dry boiler interior and ensure
continuous air
fl
ow.
4. Commission execution of inspection of boiler condition.
NOTE! Do not drain the water from boiler and heating sys-
tem when the heating season is
fi
nished or during breaks
in heating (except time necessary for possible repairs). It
protects boiler against accelerated corrosion. However, it is
necessary to drain the water from the system if break in
boiler heating occurs during frosts. It will prevent freezing
of water and damage of the system.
4.7. Cleaning and maintenance
Maintaining cleanness of the boiler is a necessary condition for
its e
ff
ective, trouble-free operation. Even small layer of deposit
will cause decrease of heat transfer from
fl
ue gas and reduces
boiler e
ffi
ciency as a result. It can be also a reason for boiler
damage.
Therefore, the boiler should be regularly and precisely
cleaned at least once a week. After shutdown and cooling down
of the boiler you should: 1. remove ash from combustion cham-
ber and ash-pan, 2. remove soot from combustion chamber and
ash-pan using wire brush, 3. after opening of upper and bottom
boiler doors clean smoke tubes and
fl
ue gas ducts with a brush,
Содержание AGRO Multi 12
Страница 1: ...Operation and maintenance manual for the boilers with feeder AGRO Multi...
Страница 22: ......
Страница 23: ......
Страница 25: ...Multi PSQ SCREW CONVEYOR FEEDER U S E R S MA N UA L Updated user s manual are available at www pereko pl...
Страница 34: ......
Страница 36: ...wer 13 12 2017 r...
Страница 38: ......
Страница 43: ...REGULATOR INSTRUCTION MANUAL ecoMAX 910R1...
Страница 53: ...USER MANUAL OF CONTROLLER INSTALLATION AND SERVICE SETTINGS ecoMAX 910R1...
Страница 59: ...23...
Страница 83: ...47...
Страница 86: ......
Страница 87: ...3 This sign indicates relation to safety issues This sign indicates relations to module functional features...
Страница 114: ......
Страница 115: ......