Operation and maintenance manual for the AGRO Multi series boilers with feeders. The producer reserves the right to introduce technical modifications.
5. Check operation of the individual equipment: a) operation
of the fan, feeder, b) activation of the central heating pump,
domestic hot water pump and
fl
oor pump, c) feeder (switch
for a change of revolutions on a box of the electric motor
should rotate to the right).
6. Turn o
ff
the fan. It feeds fuel to the feeder in manual mode.
Wait 2-3 minutes until coal appears in the feeder at the
height of air injection holes.
7. Spread the fuel aside. Place
fi
restarter and paper on it and
then pieces of small wood and
fi
re it up. After
fi
ring up the
chimney draught should suck
fl
ue gas to the convection
ducts of the boiler.
8. Start the fan and adjust air blowing to ensure uniform com-
bustions of the fuel when the wood and paper are
fi
red up.
9. When the stable
fl
ame is achieved, when heat on furnace
is generated, you should close the doors and switch the
controller to automatic mode (fan, feeder and pump/pumps
start to operate automatically). Select correct fuel from fuels
available in the controller. Flame in the furnace should have
a form of clean, intensive yellow
fl
ame. Red, smoky
fl
ame
indicates too low supply of air, while white indicates that
supply is too large. If the boiler burner operates correctly you
should set: temperature of the central heating system (usu-
ally 60-80°C), the temperature of domestic hot water (45-
55°C), the temperature of a four-way valve and temperature
of
fl
oor pump (in acc. to
Controller user’s manual
).
NOTE! Charging and cleaning doors with burner should be
tightly closed during automatic operation of the controller.
NOTE! Temperature on the boiler should not be set below
57°C! It increases a risk of occurrence of a “dew point” what
considerably low-temperature corrosion in the heat below
57°C with simultaneous use of incorrect solid fuels leads to
accelerated wear and tear of the boiler and decreases its
e
ffi
ciency exchanger. Maintaining temperature of feeding
water.
Whole combustion process will be controlled by the control-
ler when the boiler is
fi
red up (see Controller User’s Manual),
maintaining the set temperature of water in the boiler and tak-
ing into account building demand for heat.
4.3.1. Approximate output parameters
of the controller
The controller is pre-con
fi
gured, but its output parameters are
changed, depending on fuel used and may require individual
adjustments. They should be adjusted depending on heat de-
mand, type and quality (calori
fi
c value) of fuel or depending
on the development of the heating system. Selecting correct
parameters ensures economical combustion of fuel.
The most important parameters for the controller, which
controls operation of the AGRO Multi boiler are: feeding time
and break in fuel feeding. Parameters are selected depending on
the type of the product.
Fuel
AGRO Multi 12
AGRO Multi 18
AGRO Multi 26
AGRO Multi 36
AGRO Multi 52
a [s]
b [s]
c [%]
a [s]
b [s]
c [%]
a [s]
b [s]
c [%]
a [s]
b [s]
c [%]
a [s]
b [s]
c [%]
non-wood pellet
10
30
20
10
20
25
15
25
30
15
20
35
15
15
35
wheat seeds
10
30
20
10
20
25
15
25
30
15
20
35
15
15
35
a – feeding time; b – feeding break; c – fan power;
Содержание AGRO Multi 12
Страница 1: ...Operation and maintenance manual for the boilers with feeder AGRO Multi...
Страница 22: ......
Страница 23: ......
Страница 25: ...Multi PSQ SCREW CONVEYOR FEEDER U S E R S MA N UA L Updated user s manual are available at www pereko pl...
Страница 34: ......
Страница 36: ...wer 13 12 2017 r...
Страница 38: ......
Страница 43: ...REGULATOR INSTRUCTION MANUAL ecoMAX 910R1...
Страница 53: ...USER MANUAL OF CONTROLLER INSTALLATION AND SERVICE SETTINGS ecoMAX 910R1...
Страница 59: ...23...
Страница 83: ...47...
Страница 86: ......
Страница 87: ...3 This sign indicates relation to safety issues This sign indicates relations to module functional features...
Страница 114: ......
Страница 115: ......