Network Explorer
–
Burst Messages
5.5
Wired Communication Parameters
5.5.1
Interfaces > Serial
The Gateway can connect to the host system via an Ethernet interface or a Serial interface.
The parameters concerning the Serial interface can be found here. The parameters for the
Ethernet interface are described in the following section.
Figure 5.5Parameter > Wired Communication > Interfaces > Serial
NExplorer
Contents
Description
Burst Command
Displays the HART command number.
Number of
packets
Number of burst messages the selected device has sent.
Table 5.6Network Explorer
–
Burst Messages
Note!
If you are connected to the Gateway using the HART IP communication DTM (Ethernet),
make sure to update the parameters of the HART IP communication DTM (see chapter
4.6.2) when changing the following Gateway parameters:
- Parameterization > Wired Communication > Interfaces > Ethernet >
IP Address
- Parameterization > Wired Communication > Protocols > HART >
Bus Address
- Parameterization > Wired Communication > Protocols > HART >
Port Number
.