DIP switches 1 ... 4
SW1
SW2
SW3
SW4
Polling address
Note!
When using the DIP switches 5 ... 6 for setting the baud rate, this baud rate applies for the
HART protocol as well as the Modbus protocol. Alternatively you may set the baud rate
using the configuration software (see chapter 5.5.3, see chapter 5.5.4). Via software it is
possible to set the baud rate separately for HART and Modbus.
DIP switches 5 ... 6
SW5
SW6
Baud Rate
OFF
OFF
9600
ON
OFF
19200
OFF
ON
38400
ON
ON
57600
Note!
The security mode has to be enabled (DIP switch 8) to change the join key using the DTM
or web interface or to reset the join key and network ID using the buttons inside the
Gateway housing.
Caution!
Network security risk
For security reasons do not to use the security mode connection as a normal
communication channel. After having changed the join key, disable the security mode again
(DIP switch 8 = OFF).
DIP switches 7 + 8
SW7
RS-485 termination
SW8
Security mode
ON
connected
ON
enabled
OFF
disconnected
OFF
disabled