WHA-GW-*
Commissioning
22
1981
2011
-0
7
43
4.6.3
Adding Device DTM
Adding the Device DTM
1. In the project view, right-click on the entry of the communication DTM you have added in
the previous step.
2. To add the device DTM, choose
Add device
.
The
Device for
window opens (see on page 43).
Device for window with Gateway DTM
3. Select the entry
WHA-GW
.
HART IP communication DTM parameters
Corresponding Gateway parameters
Parameter
Explanation
Default
Parameter
Default
Tag
Gateway name in the
Project
view of
PACTware. Any name
may be entered (not
relevant for
connection to
gateway)
WHA-GW
–
–
Bus
Address
Gateway polling
address; must match
the settings of the
Gateway.
1
Parameterization
> Wired Communication
> Protocols > HART
>
Bus Address
1
UDP
Address
IP address of the
Gateway; must match
the settings of the
Gateway.
192.168.1.1
Parameterization
> Wired Communication
> Interfaces > Ethernet
>
IP Address
192.168.1.1
UDP Port
Gateway port number
(HART over UDP);
must match the
settings of the
Gateway.
5094
Parameterization
> Wired Communication
> Protocols > HART
>
Port Number
5094