AS-Interface
Diagnostics for AS-i Monitor and networking using AS-i Master
11.4
Diagnostics using Profile S-7.5.5
11.4.1
Binary data
11.4.2
Transparent input data
Via profile 7.5.5 it is possible to cyclically query the condition of the release cir-
cuits (OSSD Safety Control Status) of the safety monitor (Tab. 11-7). For this, it is
necessary to allocate an AS-i address (basic address) to the safety monitor, and
to reserve an 8-byte analogue input slave in the control configuration for the basic
address of the safety monitor. In these 8 bytes the diagnosis data (transparent in-
put data) is listed as in the following table:
Information!
The old diagnostics for the Safety Monitor is no longer supported.
D3
D2
D1
D0
Monitor->
Master (input)
Serial
communication
Serial
communication
1: Output 2 either
turned off or
flashing green
1: Output 1 either
turned off or
flashing green
Master->
Monitor (output)
Change from 0 to
1 resets the fault
lamp AS-i 2
Change from 0 to
1 resets Circuit 1
fault lamp
Serial
communication
Serial
communication
Tab. 11-6.
Channel
2
7
2
6
2
5
2
4
2
3
2
2
2
1
2
0
0
AS-i circuit 1
RD
YE
GN
UA
DA
EF
1
Status OSSD 2
Status OSSD 1
2
Status OSSD 6
Status OSSD 5
3
OSSD 4
OSSD 3
OSSD 2
OSSD 1
RF
YF
RF
YF
RF
YF
RF
YF
Tab. 11-7.
Channel
2
15
2
14
2
13
2
12
2
11
2
10
2
9
2
8
0
AS-i circuit 2
AU
RD
YE
GN
UA
DA
EF
1
Status OSSD 4
Status OSSD 3
2
Status OSSD 8
Status OSSD 7
3
OSSD 8
OSSD 7
OSSD 6
OSSD 5
RF
YF
RF
YF
RF
YF
RF
YF
Tab. 11-8.