AS-i Safety Monitor for 2 AS-i circuits
General
The
safe
AS-i system is intended for safety applications up to Category 4/SIL 3.
Mixed use of standard components and safety components is possible.
The AS-i Safety Monitor performs monitoring within an AS-i system of the user-
assigned safety slaves based on the configuration the user has set using configu-
ration software. In case of a Stop request or a fault condition, the AS-i Safety Mo-
nitor safety shuts off the system with a response time of maximum 40 ms.
Abb. 2-1. Safety configured and standard components in an AS-i network
Multiple Safety Monitors can be used within one AS-i system. A safe slave can be
monitored by more than one AS-i Safety Monitor.
AS-i Gateway
AS-i power supply
Safety light grid
Safety
light grid
Standard
module
Safety
E-STOP switch
Safety
module
Safety
limit switch
Standard-
Modul
AS-i Safety monitor