AS-Interface
Electrical connection
7.2
AS-i bus connection
7.3
Information about the device types
7.4
AS-i and power supply terminal assignments
Yellow ASi ribbon cable
Blue
AS-i-
Brown
AS-i+
2-conductor AS-i round cable
(Recommended: flexible power cable
H05VV-F2x1,5 per DIN VDE 0281)
Blau
AS-i-
Braun
AS-i+
Information!
Electrical work is to be performed only by electrical technicians.
Information!
A listing of the individual devices and their features can be found in section Product
information.
Information!
The cable indicated by grey must not have slaves or repeaters connected to it.
The yellow cable must not have AS-i power suppliers or additional masters connected
to it.
Information!
The function ground should be made with as short a cable as possible to ensure good
EMC characteristics.
Attention!
The AS-I power supply for the AS-I components must have isolation per IEC 60 742
and be able to handle momentary power interruptions of up to 20 ms. The power sup-
ply for the 24 V supply must also have isolation per IEC 60 742 and be able to handle
momentary power interruptions of up to 20 ms. The maximum output voltage of the
power supply must also be less than 42 V in case of a fault.