AS-Interface
Function and startup of the Safety Monitor
•
A PIN is a 4-digit number and can only be changed from the display, not via
the
ASIMON 3 G2
software.
•
After entering the PIN, the display can be used to start a teaching procedure
for the code sequences. The monitor stops immediately after entering the
PIN. After teaching, the monitor starts after a prompt and acknowledgement
on the display.
Legend: "
3
" = possible; "–" = not possible
Code sequences for releasing a configuration do not necessarily have to have
been successfully learned. It is also possible to release without code sequences,
which must then be learned at a later time.
Teaching the code sequences is simple to perform:
•
Using the ESC/Service key (See section Replacing a defective safety-confi-
gured AS-i slave)
or
•
Using the display (See section TEACH CODES).
8.6.2
Function of the ESC/Service key
In traditional (classical) display mode, the ESC/Service key takes on two kinds of
functions:
•
Briefly pressing the ESC/Service key unlocks the Safety Monitor when red is
flashing
Information!
For additional information see sectionReplacing a defective safety-configured AS-i
slave.
Action
ASIMON Software
On AS-i Safety Monitor
Configure and load into Safety
Monitor
3
3
(only from chip card)
Stopping
3
3
Releasing
3
–
Starting
3
3
Teaching code sequences
3
3
Changing the password
3
3
(only from chip card)
Changing the PIN
–
3