E
LECTRICAL
C
ONNECTIONS
9
3.
Electrical Connections
The terminals should be tightened with a slotted screwdriver (blade width 2 mm).
3.1
DC Voltage Supply (X1)
The device can be supplied with a DC voltage between 18 and 30 V DC via
terminal X1 pins 1 and 2. The current consumption depends, among other things,
on the level of the supply voltage and the settings and is approx. 50 mA, plus the
rotary encoder current taken from the auxiliary voltage output.
All GND connections are connected internally.
3.2
Auxiliary Voltage Output (X2)
Two auxiliary voltages 24 V DC and 5 V DC are available as encoder/sensor
supply at terminal X2 pins 7, 8, and 9. The 24-V DC output voltage depends on
the device supply (see Technische Daten).