O
PERATING
S
OFTWARE
OS6.0
/
OS10.0
39
AVERAGE FILTER—POSITION
(filter for average determination)
Switchable average determination for preventing position fluctuations
.
Value
Function
0
No average determination
1
Flowing average determination with two cycles
2
Flowing average determination with four cycles
3
Flowing average determination with eight cycles
4
Flowing average determination with 16 cycles
STANDSTILL TIME(s)
This parameter defines the downtime. When downtime is detected, a downtime
signal is signaled after xx.xx seconds and the startup override is reactivated.
Downtime monitoring can be set in the PRESELECTION MENU.
AVERAGE FILTER—SPEED (filter for average determination)
Switchable average determination for preventing velocity fluctuations.
Value
Function
0
No average determination
1
Flowing average determination with two cycles
2
Flowing average determination with four cycles
3
Flowing average determination with eight cycles
4
Flowing average determination with 16 cycles
Value
Function
0.01
Shortest delay time in seconds
…
99.99
Longest delay time in seconds
Содержание K23-SSI/Rx/IU-C
Страница 1: ...Your automation our passion K23 SSI Rx IU C Signal converter Manual...
Страница 77: ...APPENDIX 77 5 6 Reading in the SSI Value The received data is always filled internally to a 32 bit data length...
Страница 79: ...APPENDIX 79 Calculating the SSI Zero Position Checking the direction of rotation Evaluating the bit suppression...
Страница 80: ...APPENDIX 80 Calculating the SSI offset Calculating the display value...
Страница 83: ...APPENDIX 83 5 8 Dimensions...
Страница 84: ...www pepperl fuchs com Subject to modifications Pepperl Fuchs Printed in Germany DOCT 6641...