7.4
Set Application Flag Inclination for x-Axis
Assumption:
•
Device node ID: 0x80 (default)
•
Master node ID: 0x01
Step 1: Starting Parameter Mode
See also chapter "Starting Parameter Mode"
xx: unused, bytes optional
Effect
Parameter Mode is started.
•
Message: D0 = Password accepted (see also chapter "J1939 Interface Description", sec
-
tion "Answer Messages").
•
Yellow LED blinks
•
No more PDOs are sent
Step 2.1: Writing Parameter Index 0x81
See also chapter "J1939 Interface Description", section "Writing Parameters"
xx: unused, bytes optional
Effect
New parameter is acknowledged.
•
Answer message: D0 81 01 = parameter (0x81) successfully written with new value "1"
(see also chapter "J1939 Interface Description", section "Answer Messages").
•
Yellow LED blinks
•
No more PDOs are sent
Identifier
Data Bytes
Priority
PGN
Source
address
1
CMD
2
Pass
-
word
3
4
5
6
7
8
0x00
0xEF80
0x01
0xEB
(CMD:
Start
param
-
eter
mode)
0x55
xx
xx
xx
xx
xx
xx
Table 7.11
Identifier
Data Bytes
Priority
PGN
Source
address
1
CMD
2
Index
3
4
5
6
7
8
0x00
0xEF80
0x01
0xE1
(CMD:
Write
param
-
eter)
0x81
(Param
_AF_In
-
cl_x_
-
Mode)
0x01
(Single
Point)
xx
xx
xx
xx
xx
Table 7.12