Inertial Measurement Unit IMUF99*B20
Installation
3
Installation
3.1
Electrical connection
The IMU360D-F99 is equipped with 2 connectors M12 x 1, 5-pin, male and female for CAN bus
integration. If a terminator is required, it muss be attached externally on the female connector.
Therefore e. g. "Terminator ICZ-TR-CAN/DN-V15" from Fuchs is available (also see
datasheet of the sensor).
Connecting the sensor to the voltage
1.
Connect the operating voltage to pins 2 and 3 of the 5-pin connector.
The "Power" LED lights up green.
Pin
Wire color
Designation
1
Brown
Not used
2
White
+UB
3
Blue
GND
4
Black
CAN-H
5
Gray
CAN-L
Table 3.1
Connector assignment
1
n.c.
2
3
+UB
GND
CAN-L
4
5
CAN-H
Note
The wire colors listed above apply when one of the bus cables from the Fuchs
accessories range is used.
Note
The device complies with the EMC norms and standards described in the datasheets. If
necessary, additional external EMC protection elements and interference suppression
measures (e.g. filters) are recommended.
Warning!
Damage to the device
Connecting an alternating current or excessive supply voltage can damage the device or cause
the device to malfunction.
Electrical connections with reversed polarity can damage the device or cause the device to
malfunction.
Connect the sensor to direct current (DC). Ensure that the supply voltage rating is within the
specified sensor range. Ensure that the connecting wires on the cordset in use are connected
correctly.