Parameterization and Operation
4.6.3
Enabling/Disabling Hardware Channels 2, 3, 5, 6, 8, 9, 11, 12
Use the Sensor A Mode and Sensor B Mode parameters to individually enable or disable the
channels 2, 3, 5, 6, 8, 9, 11, 12.
4.6.4
Lead Fault Monitoring
You can independently enable or disable lead short circuit and lead breakage monitoring of the
sensor connections with the Lead Fault Monitoring parameter.
The Lead Fault parameter contains the fault status of the sensor connection. Structure and
content is identical to the Lead Fault Monitoring parameter.
Transducer
Block
Hardware Channel
Sensor A Mode
Sensor B Mode
1
2
3
2
5
6
3
8
9
4
11
12
Option
Description
Hardware Inputs
Short Circuit Sensor-A
Enable/disable lead short
circuit detection for position
feedback sensor
–
sensor A connection
TB1: 2
TB2: 5
TB3: 8
TB4: 11
Lead Breakage Sensor-A
Enable/disable lead breakage
detection for position
feedback sensor
–
sensor A connection
Short Circuit Sensor-B
Enable/disable lead short
circuit detection for position
feedback sensor
–
sensor B connection
TB1: 3
TB2: 6
TB3: 9
TB4: 12
Lead Breakage Sensor-B
Enable/disable lead breakage
detection for position
feedback sensor
–
sensor B connection
Short Circuit Sensor
Enable/disable lead short
circuit detection for sensor
connection
TB1: 1
TB2: 4
TB3: 7
TB4: 10
Lead Breakage Sensor
Enable/disable lead breakage
detection for sensor
connection