2
017-
06
18
Installation and Commissioning
F2D0-MIO* Input/Output Cable Glands
F2D0-MIO* Fieldbus Cable Gland
Sensor Entries Clamping Ranges: Torques
Cable Entry Option
CG or Plug
Type
S1+S2+S3
S1+S2
S1
Body
00
1 x M20, 8 x
M16 sealing
plug plastic
SP.PE.M16.PA.
C
-
-
-
1.5 Nm
01
1 x M20, 8 x
M16 sealing
plug stainless
steel
SP.MD.M16.SS.
C
-
-
-
4 Nm
02
1 x M20, 8 x
M16 cable
glands plastic
CG.PIDS.M16S
.PA.C.10
-
4
…
5 mm:
3.5 Nm
5
…
8 mm:
4 Nm
1.5 Nm
03
1 x M20, 8 x
M16 cable
glands nickel
plated brass
CG.NA.M16.BN
.C
4
…
6 mm:
20 Nm
6
…
9 mm:
18 Nm
9
…
12 mm:
15 Nm
4 Nm
04
1 x M20, 8 x
M16 cable
glands stainless
steel
CG.NA.M16.SS
.C
4
…
6 mm:
20 Nm
6
…
9 mm:
18 Nm
9
…
12 mm:
15 Nm
4 Nm
05
5 x M20 cable
glands plastic
CG.PIDS.M20.
PA.C.10
-
6
…
8.5 mm:
5 Nm
7
…
12 mm:
5 Nm
2 Nm
Table 3.1
The torques that are actually required depend on the clamping range. This range is
determined by the diameter of the cable and the resulting seal combinations (S1+S2+S3,
S1+S2, S1) used with the cable gland or plug. For details see the documentation on the
cable gland or plug type available at www.pepperl-fuchs.com.
Fieldbus Entries Clamping Ranges: Torques
Cable Entry Option
CG or Plug
Type
S1+S2+S3
S1+S2
S1
Body
00
1 x M20, 8 x
M16 blind plug
plastic
SP.PE.M20.PA.
C
-
-
-
2 Nm
01
1 x M20, 8 x
M16 blind plug
stainless steel
SP.MD.M20.SS.
C
-
-
-
5.5 Nm
02
1 x M20, 8 x
M16 cable
glands plastic
CG.PEDS.M20.
PA.C.10
-
6
…
8.5 mm:
5 Nm
7
…
12 mm:
5 Nm
2 Nm
03
1 x M20, 8 x
M16 cable
glands nickel
plated brass
CG.NA.M20S.B
N.C
4
…
6 mm:
20 Nm
6
…
9 mm:
18 Nm
9
…
12 mm:
15 Nm
5.5 Nm
04
1 x M20, 8 x
M16 cable
glands stainless
steel
CG.NA.M20S.S
S.C
4
…
6 mm:
20 Nm
6
…
9 mm:
18 Nm
9
…
12 mm:
15 Nm
5.5 Nm
05
5 x M20 cable
glands plastic
CG.PEDS.M20.
PA.C.10
-
6
…
8.5 mm:
5 Nm
7
…
12 mm:
5 Nm
2 Nm
05
5 x M20 cable
glands plastic
SP.PE.M20.PA.
C
Unused thread
2 Nm
Table 3.2
The torques that are actually required depend on the clamping range. This range is
determined by the diameter of the cable and the resulting seal combinations (S1+S2+S3,
S1+S2, S1) used with the cable gland or plug. For details see the documentation on the
cable gland or plug type available at www.pepperl-fuchs.com.