Reference List of MIO Parameters
6
Reference List of MIO Parameters
List of Parameters, Legend
Char.: The column Char. shows characteristics or conditions applicable to this parameter.
These are:
■
OOS: Out of Service. The parameter can be written only if the target mode of the block is
"Out of Service".
■
S: Static. During each writing process an identified parameter of this type, the ST_REV
parameter is increased by one.
■
W: Writeable. The parameter can be modified by the user.
■
R: Readable. As all parameters can be read, this is not marked explicitly.
Transducer Block
Parameter
Char.
Description
Breakaway Time Close ->
Open
The last breakaway time measured from "closed" to
"open". This value is not stored on the device, i. e.,
this value is available after a power failure only after
opening and closing the valve once.
Breakaway Time Close ->
Open Setpoint
W
S
Reference value for the breakaway time from
"closed" to "open".
Range of values:
■
Reference value: 0 s ... 60 s
■
Maximum admissible deviation: 0 % ... 100 %
Breakaway Time Open ->
Close
The last breakaway time from measured "open" to
"closed". This value is not stored on the device, i. e.,
this value is available after a power failure only after
opening and closing the valve once.
Breakaway Time Open ->
Close Setpoint
W
S
Reference value for the breakaway time from "open"
to "closed".
Range of values:
■
Reference value: 0 s ... 60 s
■
Maximum admissible deviation: 0 % ... 100 %
Counter Value
Counter value as float value with status information.
Cyclic Test Period
W
S
If the reference value of the valve is not modified for
this time, a cyclic function test is carried out.
Applicable if activated.
MIO Mode
This parameter contains the MIO device mode
defined in the resource block parameter MIO Mode.
Primary Value
The valve position which is transferred to the function
block.
PV_D Generation
W
S
OOS
If the signals of the final position feedback are
evaluated, this parameter determines how to further
process the evaluated signals prior to transferring
them to the function block.
RELATED_HW_CHANN
ELS
Contains the specific connected hardware inputs to a
transducer block.
TB1: hardware input 1, 2, 3
TB2: hardware input 4, 5, 6
TB3: hardware input 7, 8, 9
TB4: hardware input 10, 11, 12
Sensor A Mode
W
OOS
In MIO binary mode: Enabling/disabling of the
hardware group 2 channels:
TB1:2, TB2:5, TB3:8, TB4:11