Reference List of MIO Parameters
Resource Block
Transit Time Open ->
Close
The last transit time measured from "open" to
"closed". This value is not stored on the device, i. e.,
this value is available after a power failure only after
opening and closing the valve once.
Transit Time Open ->
Close Setpoint
W
S
Reference value for the transit time from "open" to
"closed".
Range of values:
■
Reference value: 0 s ... 180 s
■
Maximum admissible deviation: 0 % ... 100 %.
Valve Error
Parameter indicates mechanical valve faults that the
transducer block recognized.
Valve ID
W
S
Valve model: Valve design.
Valve Info
Valve information: Parameter indicates the
information of the current status of the valve or
transducer block.
Valve Man.
W
S
Valve manufacturer: Name of valve manufacturer.
Valve Model
W
S
Product name of the valve.
Valve Monitoring
W
S
Time measurement for the valve, stroke counter, and
the cyclic function tests can be activated in this
parameter.
Valve Position
Parameter indicates the current valve position:
closed, open, intermediate, unknown.
Valve Position Extended
Parameter indicates the current valve position with
additional information such as "valve opening" and
"valve closing" if the valve is in the intermediate
position.
Valve Serial Number
W
S
Serial number of the valve.
Valve Type
W
S
Describes the type of valve: linear, turning, other,
undefined.
Valve Warning
Parameter that indicates that the measured transit or
breakaway time is higher or lower than the reference
value including the maximum admissible deviation.
Parameter
Char.
Description
BI_CYCLE_TIMES
Parameter that contains the overall measurement
cycle times for the indivual group 1 and group 2
hardware channels.
MIO_MODE
W
S
OOS
Defines the MIO mode in which the device operates:
1. Valve coupler
2. Binary Input
3. Frequency Input
4. Counter