2
017-
06
50
Troubleshooting and Diagnosis
XD Error
Mechanical error
The combined error
signal of the errors is
displayed in the Valve
Error parameter.
See Valve Error
parameter.
Valve Lead Fault
The combined error
signal of the errors is
displayed in the Valve
Lead Fault Monitoring
parameter.
See Valve Lead Fault
Monitoring parameter.
Sensor Lead Fault
The combined error
signal of the errors is
displayed in the Sensor
Lead Fault Monitoring
parameter.
See Sensor Lead Fault
Monitoring parameter.
Valve needs
Maintenance
Set if one of the Valve
Warning parameter
conditions occurs.
See Valve Warning
parameter.
Stroke Count Limit
Stroke Counter Limit is
exceeded.
Maintain or replace the
valve.
Valve Warning
Breakaway time ... too
long
Transit time ... too long
(... = C -> O or O -> C)
The measured time
exceeded the reference
value plus the
admissible allowance.
■
Check auxiliary
power.
■
Check reference
times and
allowances.
■
Check final position
feedback contacts
for proper
functioning.
■
Check friction of
valve.
Breakaway time ... too
short
Transit time ... too
short
(... = C -> O or O -> C)
The measured time
undercut the reference
value minus the
admissible allowance.
■
Check auxiliary
power.
■
Check reference
times and
allowances.
■
Check final position
feedback contacts
for proper
functioning.
■
Check friction of
valve.
Problem
Troubleshooting