Solar T°
SB-PD-PRO-004B
12V
Current T°
of pool water
Current T°
of solar probe
Set point T° for
Speedeo
heating
Temp. difference
Delta heating
Preferred T°
for solar power
OUT 1
OUT 2
COMM. SPEED 1 SPEED 2 SPEED 3 SPEED 4
BUS
IN 1
IN 2
OUT 3
N
L
230 V ~
AUTO:
Activates solar heating and uses all available calories.
Temp difference:
Difference between solar T°/pool T° which activates the solar heating.
Delta heating:
Decreases T° set point for non-solar heating, so that solar heating can be the
primary type used.
1 - Connect the cables in accordance with the diagram.
2 - Start the secured
Install menu
(from the main menu, simultaneously hold down
Esc
and
Valid
for 3 secs. A star appears
in the top right corner of the home screen).
3 - On the
Inlets / E2
sub-menu, select
Solar T°
to indicate that the SB-PD-PRO-004B temperature sensor is connected to the
corresponding inlet
.
4 - On the
Outlets / S1-S2-S3
sub-menu (in accordance with chosen terminal), select
SOLAR
to indicate that a solar heater is
connected to the corresponding outlet
.
5 - On the
Temperature / Solar
sub-menu, configure the settings:
Outlet: solar heating connection
-Solar : AUTO
Temp difference :4°C
Delta heating :-2°C
An outlet is a dry contact and
does not supply any voltage.
21