OUT 1
OUT 2
COMM. SPEED 1 SPEED 2 SPEED 3 SPEED 4
BUS
IN 1
IN 2
OUT 3
N
L
230 V ~
185 mm
150 mm
Ø 8/8.8 mm
30 mm max.
5 mm
Ø 8/8.8 mm
30 mm max.
5 mm
= RO2V (3 x 1.5 mm
2
min.)
= RO2V (2 x 1.5 mm
2
min.)
POWER SUPPLY 230 V / 50 Hz +- 10%
OUT 1 - 230 V 10A max.
OUT 2 - 230 V 10A max.
OUT 3 - 230 V 10A max.
Compatible power supply cables 230 V
Compatible dry contact cables
Cable ducts
- must be installed if an outlet is in use,
(to stop any humidity or acidic vapour entering)
Caps
- must be installed if an outlet is not in use
(to stop any humidity or acidic vapour entering)
- The device must be installed by a qualified technician according to valid local regulation
- This device is permanently connected.
- The power supply to the device is cut by its interrupter, which must be close and must remain
accessible at all times.
- The device needs to be connected to the earth and its power supply needs to be protected by 16A 30
mA differential protection. This protection must be cut before any intervention on the device.
- Overvoltage category II (2,500 V peak) electrical device. If necessary, place overvoltage protection
equipment before the device.
- The device must be placed close to the electrical cabinet to aid connections (3 m max.).
Electrical connections regulation
Interchangeable fuse
FST 5x20 250 V AC 1A 5x20 fast
Screw terminals
Slotted screwdriver 2.5 mm/0.5-0.6 Nm
REAR VIEW
The supply cable as well as the cables of the
dry power contacts must be placed in a plated
and closed channel under the device.
08