Installer manual Fleck 3150 NXT/NXT2 - Programming
64 / 182
Ref. MKT-IM-010 / C - 18.10.2019
6.1.5
Master programming mode
Info
As soon as programming mode is entered, all parameters can be displayed or set to
suit the needs. Depending on the current programming, some functions will not be
displayed or will not be changeable.
Info
If none of the buttons are pushed for 5 minutes in the Programming mode, or if there is
a power failure, the controller returns to Service mode without saving.
Mandatory
In order to store the new settings in the programming mode, it is necessary to go
through all the parameters.
6.1.5.1
Master programming mode chart
Parameter
Options
Definition
Note
LANGUAGE
ENGLISH
English
FRANCAIS
French
DEUTSCH
German
ITALIANO
Italian
ESPANOL
Spanish
SYSTEM TYPE
4
Single unit
1 unit.
5
Parallel interlock
2 to 4 units.
6
Parallel series
regeneration
7
Alternating immediate 2 units.
9
Parallel with standby
unit
2 to 4 units.
14
On-demand
VALVE
ADDRESS
#1
First control valve
This screen will not be displayed
for system type 4.
#2
Second control valve
(default)
#3
Third control valve
#4
Fourth control valve
SYSTEM SIZE
2
2 valves in the system This screen will not be displayed
for system type 4.
3
3 valves in the system
4
4 valves in the system
Содержание FLECK 3150 NXT
Страница 1: ...FLECK 3150 NXT NXT2 INSTALLER MANUAL WATER PURIFICATION ...
Страница 137: ...Installer manual Fleck 3150 NXT NXT2 Maintenance Ref MKT IM 010 C 18 10 2019 137 182 AC motor DC motor ...
Страница 139: ...Installer manual Fleck 3150 NXT NXT2 Maintenance Ref MKT IM 010 C 18 10 2019 139 182 DC motor ...
Страница 141: ...Installer manual Fleck 3150 NXT NXT2 Maintenance Ref MKT IM 010 C 18 10 2019 141 182 AC motor DC motor ...
Страница 144: ...Installer manual Fleck 3150 NXT NXT2 Maintenance 144 182 Ref MKT IM 010 C 18 10 2019 ...
Страница 148: ...Installer manual Fleck 3150 NXT NXT2 Maintenance 148 182 Ref MKT IM 010 C 18 10 2019 ...
Страница 182: ...www pentairaquaeurope com ...