![Pego 100N MASTER3 SC600 Скачать руководство пользователя страница 45](http://html1.mh-extra.com/html/pego/100n-master3-sc600/100n-master3-sc600_use-and-maintenance-manual_1522019045.webp)
VISION SC600
Pag. 45
Rev. 02-18
USE AND MAINTENANCE MANUAL
100N MASTER3 CONNECTION LAYOUT
Power supply
PIN
TERMINAL
DESCRIPTION
1
– 2
N
– L
Power supply
115÷230Vac ±10% 50/60Hz
C
onsumption: 20 VA max.
45
Connect ground to terminal 45 of the console (functional earth). This
connection helps to limit the effects of electromagnetic noise on the
control system. The ground connection must be made in a manner
consistent with applicable regulations.
Digital outputs
PIN
TERMINAL
RELAY OUTPUTS FEATURES
(Voltage free contacts)
DESCRIPTION
3
– 4
Relay 30A 240V~ (AC1)
10A 240V~ (AC3) (2HP)
Compr. 1 / Partition 1 / Fan 1
5
– 6
Relay 16A 240V~ (AC1)
3A 240V~ (AC3)
Compr. 2 / Partition 2 / Fan 2
7
– 8
Relay 16A 240V~ (AC1)
3A 240V~ (AC3)
Compr. 3 / Partition 3 / Fan 3
9
– 10
Relay 16A 240V~ (AC1)
3A 240V~ (AC3)
Compr. 4 / Partition 4 / Fan 4
11
– 12
Relay 16A 240V~ (AC1)
3A 240V~ (AC3)
Compr. 5 / Partition 5 / Fan 5
13
– 14
Relay 16A 240V~ (AC1)
3A 240V~ (AC3)
Compr. 6 / Partition 6 / Fan 6
15 - 16
Relay 16A 240V~ (AC1)
3A 240V~ (AC3)
Compr. 7 / Partition 7 / Fan 7
17
– 18
Relay 16A 240V~ (AC1)
3A 240V~ (AC3)
Alarm relay
19
– 20
Relay 16A 240V~ (AC1)
3A 240V~ (AC3)
Not used
21
– 22
Relay 16A 240V~ (AC1)
3A 240V~ (AC3)
Compr. 10 / Partition 10 / Fan 10
Attachments
A.2