VISION SC600
Pag. 12
Rev. 02-18
USE AND MAINTENANCE MANUAL
MUTE ALARM
Reset sound alarm if any. If pressed more than 3 seconds displays the
alarm history.
UP
Increases the values / Scroll up the parameters
KEYS COMBINATIONS
+
EXIT PROGRAMMING
If pressed simultaneously for more than 3 seconds within
any programming menu or the historical alarm allow you
to exit the menu.
Exit from menu generates a confirmation beep.
+
1st LEVEL PROGRAMMING
If pressed simultaneously for more than 3 seconds allow
access to the first level programming menu (if you are not
in programming). Exit from this menu takes place
automatically after 30 seconds of keyboard inactivity or
by pressing up arrow + down arrow (confirmation beep
output).
+
+
2nd LEVEL PROGRAMMING
If pressed simultaneously for more than 3 seconds allow
access to the second level programming menu.
At the entrance of the menu a confirmation beep is
generated.
+
+
+
3rd LEVEL PROGRAMMING
If pressed simultaneously for more than 3 seconds allow
access to the third level programming menu.
At the entrance of the menu a confirmation beep is
generated.
+
OUTPUT HOUR COUNTER / ALARM HISTORY RESET
While viewing the working time of an output within the
read-only Hr1, Hr2, Hr3, Hr4, Hr5, Hr6, Hr7, Hr8, Hr9,
Hr0 parameters while pressing the SET_COMP key and
pressing the "SET_VENT" for at least 10 seconds, the
hour counter will be reset.
Similarly while viewing the alarm history while pressing
the SET_COMP key and pressing the "SET_VENT" for at
least 10 seconds, the alarm history will be reset.
5.3
CHAP. 5 - Data programming