VISION SC600
Pag. 20
Rev. 02-18
USE AND MAINTENANCE MANUAL
Ad
Network address
for connection to the
TeleNET or Modbus supervision system
(see chap. 6.1)
0 ÷ 31 (con SEr=0)
1 ÷ 247 (con SEr=1)
1
SEr
RS-485 communication protocol
0 = TeleNET protocol
1 = Modbus-RTU protocol
0
bdr
Modbus baudrate.
0 = 300 baud
1 = 600 baud
2= 1200 baud
3 = 2400 baud
4 = 4800 baud
5 = 9600 baud
6 = 14400 baud
7 = 19200 baud
8 = 38400 baud
5
Prt
Modbus parity checking
0 = no parity bit
1 = even parity bit
2 = odd parity bit
0
P1
Password: kind of protection
(active when PA is not 0)
0 = shows only the set point and
permits deactivation of the alarms.
1 = disables access to levels 1, 2
and 3 programming and disables
access to alarm history (access
permitted to all other functions)
2 = disables access to levels 2 and
3 programming (access permitted
to all other functions).
3 = disables access to level 3
programming (access permitted to
all other functions).
3
PA
Password
(see P1 for the type of protection)
0
999
0 = function disabled
0
hMS
Time setting
00:00
23:59
0
dY
Day setting
01
31
01
Mo
Month setting
01
12
01
Yr
Year setting
00
99
13
dEF
Reserved parameter
- - -
Read only
reL
Software release
Read only
CHAP. 5 - Data programming