USE AND MAINTENANCE MANUAL
LEVEL 2 PROGRAMMING (Installer level)
In order to access the 2
nd
programming Level, press and hold the UP key
(
)
, the DOWN
key
(
)
and the STAND-BY key for over 3 seconds.
When the first programming variable appears:
1.
Select the variable you want to change with the key
(
)
or with the key
(
)
. After
selecting the required variable, it is possible to edit configuration by pressing and holding
the SET key and pressing either the
(
)
or
(
)
key.
2.
After setting the configuration values, press and hold both the
(
)
key and the
(
)
key
for a few seconds until the pressure value appears and exit the menu.
3.
Any changes made to the variables are saved automatically when the system closes the
configuration menu.
4.
Press the STAND-BY key to enable the control.
LIST OF LEVEL 2 VARIABLES (Installer Level)
LABEL
MEANING
VALUES
DEFAULT
SEq
Logical selection of the digital outputs
activation
0 = With rotation
1 = Without rotation
1
Man
Max. number (hours x 10) of operating
hours
for a compressor after which a
request for maintenance will be signaled.
(if = 0, the request for maintenance will not
be signaled)
0 ÷ 510
step 2
300
rA
Setting general alarm output
1 = alarm relay(17-18) energized
in alarm.
0 = alarm relay (17-18) disabled.
-1 = alarm relay (17-18)
de-energized when in alarm.
1
PU4
Pressure (bar) corresponding to 4mA
Referred to the high pressure probe.
-1,0 ÷ (PV2 - 0,1)
0,0
PU2
Pressure (bar) corresponding to 20mA
Referred to the high pressure probe.
(PV4 + 0,1) ÷ 50,0
30,0
PC4
Pressure (bar) corresponding to 4mA
Referred to the low pressure probe.
-1,0 ÷ (PC2 - 0,1)
0,0
PC2
Pressure (bar) corresponding to 20mA
Referred to the low pressure probe.
(PC4 + 0,1) ÷ 50,0
12,0
NiP
Time (hours) in which the activation of
the manual central alarm is triggered 5
times.
At the 5th activation, it remains in alarm.
0
240 hours
6 ore
5.11
CHAP. 5 - Data programming