ALL
View of the last alarm triggered
Alarm code
Read only
A1C
Minimum compressor pressure alarm
The absolute pressure referring to the
Intake probe below which, once the Ald
delay time is activated, the LOW pressure
alarm is triggered showing
ELc
alternating
with the pressure on the display and the
flashing of the alarm icon.
When the alarm turns off, the "alarm
presence" icon will remain lit to indicate
which operation has occurred until the
alarm button is pressed.
-0,6 ÷ (A2C-0,2)
Bar, step 0,2 Bar
-0,6 bar
A2C
Maximum compressor pressure alarm
The absolute pressure referring to the
Intake probe above which, once the Ald
delay time is activated, the HIGH pressure
alarm is triggered showing
EHc
alternating
with the pressure on the display and the
flashing of the alarm icon.
When the alarm turns off, the "alarm
presence" icon will remain lit to indicate
which operation has occurred until the
alarm button is pressed.
(A1C+0,2) ÷ +30,0
Bar, step 0,2 Bar
+30,0 bar
A1U
Minimum fan pressure alarm
The absolute pressure referring to the
delivery probe below which, once the Ald
delay time is activated, the LOW pressure
alarm is triggered showing
ELu
alternating
with the pressure on the display and the
flashing of the alarm icon.
When the alarm turns off, the "alarm
presence" icon will remain lit to indicate
which operation has occurred until the
alarm button is pressed.
-0,6 ÷ (A2U-0,2)
Bar, step 0,2 Bar
-0,6 bar
A2U
Maximum fan pressure alarm
The absolute pressure referring to the
delivery probe above which, once the Ald
delay time is activated, the HIGH pressure
alarm is triggered showing
EHu
alternating
with the pressure on the display and the
flashing of the alarm icon.
When the alarm turns off, the "alarm
presence" icon will remain lit to indicate
which operation has occurred until the
alarm button is pressed.
(A1U+0,2) ÷ +30,0
Bar, step 0,2 Bar
+30,0 bar
tdS
Day start time programming
(ignored if
dnE=0 or there is a night digital input)
00:00 ÷ 23:59
06:00
tdE
Day end time programming
(ignored if
dnE=0 or there is a night digital input)
00:00 ÷ 23:59
22:00
CHAP. 5 - Data programming