VISION SC600
Pag. 19
Rev. 02-18
USE AND MAINTENANCE MANUAL
rLo
Time (min.) with which the freon/oil pre-
alarm (Ep) becomes alarm (EF).
Once this
time has passed, all outputs are disabled.
0
240 min
30 min
iOu
Offset Inverter fans (of pressure)
Value always less than (r0V) value
0,5
2,5 bar
always < r0U
0,5
iMu
Inverter fans: minimum 0-10V output
value setting
0
100 %
30 %
bOu
Boost fans: Time for which the 0-10V
output of the fans is pushed to 100%.
This is used to win the breakaway at
their start.
(SECONDS)
0
240 sec
2 sec
iMc
Inverter compressors: minimum
0-10V output value setting
0
100 %
30 %
itS
Minimum time to change analog output
inverter compressor to go from 0 to 10V
or 10 to 0V
during activation or deactivation
of compressors steps.
(SECONDS)
0
240
60
LSC
Minimum value that can be attributed to
the Compressors set point
-0,5
(HSC-1)
0,2
HSC
Maximum value that can be attributed to
the Compressors set point
(LSC+1)
10,0
5,0
LSU
Minimum value that can be attributed to
the Fans set point
0,0
(HSU-1)
10.0
HSU
Maximum value that can be attributed to
the Fans set point
(LSU+1)
30,0
25,0
dnE
Night mode enable (energy saving)
At night operation decimal point flashes.
0 = disabled
1 = enabled
0
nSC
Correction for the compressor SET
during night operation (energy saving)
During night operation the Compressor set
is:
Compressor Set = Set comp. + nSC
-5,0
5,0 Bar
0,0
nSU
Correction for the fans SET during night
operation (energy saving)
During night operation the fans set is:
Fans Set = Set fans + nSU
-10,0
10,0 Bar
0,0
Ald
Minimum or maximum pressure alarm
signaling and display delay time.
0
240 min
120 min
CLC
Adjustment compressors sensor
calibration
(low pressure)
-10,0
+10,0
step 0,1 bar
0,0
CLV
Adjustment fans sensor
calibration
(high pressure)
-10,0
+10,0
step 0,1 bar
0,0
BEE
Buzzer enable
0 = disabled
1 = enabled
1