34
| ENGLISH
DISPLAY
PARAMETERS
DESCRIPTION
u.m. Default Min
Max
Step
Pd 70
iDRY PRESSURE (%)
Sets the value of the minimum pressure
(expressed as the % of the SET pressure)
which must be reached when there is no
flow as otherwise the dry running alarm
is activated.
%
70
10
100
1
FM
FLAT ADJUSTMENT
Activates/deactivates the FLAT modulation;
the FLAT modulation reduces the heating
of the power components of the inverter
-
1
0
1
1
SET.F
RESETTING
OF FACTORY
PARAMETERS
By means of this function the parameters entered in the BASE and ADV lists are
reset at the factory values. ATTENTION: DO NOT USE THIS FUNCTION in the UPV-OS
pumping units as these models have a special setting.
In order to reset the parameters press the SET switch and keep it pressed until “OK”
appears on the display (SET
Æ
****
Æ
OK)
INSPECTION LIST (INSP)
The INSP (Inspection) list allows one to visualise the history of functioning of the inverter, in particular the hours of functioning,
the number of start times, the registration of the alarms.
INSP
WH
HOURS OF FUNCTIONING
OF THE PUMP
Hours of functioning of the pump (motor switched on
TH
HOURS INVERTER
SWITCHED ON
Hours of functioning (device switched on, with pump
functioning or in STAND-BY)
NS
TOTAL NUMBER OF
STARTS
Number of starts of the pump, from the time of
installation.
SH
AVERAGE NUMBER OF
STARTS
Average number of starts each hour the inverter is
switched on
E1
LAST ERROR
Last error registered
E1H
HOUR OF LAST ERROR
Hour last error registered (referred to TH)
E2
PENULIMATE ERROR
Penultimate error registered
E2H
HOUR OF PENULTIMATE
ERROR
Hour penultimate error registered (referred to TH)
E3
THIRD LAST ERROR
Third last error registered
Follows
i
Содержание TISSEL-100
Страница 2: ......
Страница 77: ...77 30 5 TISSEL 100 TISSEL 100 OFF ON...
Страница 80: ...80 30 TISSEL 100 TISSEL 100 10 Qmax 80 V 80 x 10 8 70 Pset 4 4 x 70 2 8 TISSEL 100 230 50...
Страница 83: ...83 BASIC P 2P A RO ADV d MF LF HF Td PF TPF TP TF RF FS US EI i...
Страница 84: ...84 EO AI AT W V Pd iDRY FM FLAT SET F INSP WH TH NS SH E1 E1H E2 E2H E3 E3H E4 E4H EE TEST...
Страница 92: ...92 OVERTEMP MODULE COM ERROR LOW LEVEL EXT OFF 2 Prestazioni della pompa inferiori a quelle di targa...
Страница 94: ......
Страница 95: ......