31
ENGLISH |
SETTING THE BASIC PARAMETERS)
It is imperative the
BASIC PARAMETERS
for the configuration of the inverter are set during the installation.
BASIC
DISPLAY
PARAMETERS DESCRIPTION
u.m. Default Min
Max
Step
P 3.5
SET PRESSURE
(bar)
Sets the value of the constant
pressure
in the plant
.
bar
3.5
1
10
0.1
psi
50
15
130
1.5
2P 2.5
SECOND SET
PRESSURE
(bar)
Sets a second pressure value.
To activate it the EI parameter must be
configured in the advanced parameters
bar
2.5
1
10
0.1
psi
50
15
130
1.5
A 6.0
MOTOR CURRENT (A)
Sets the nominal current of the motor on exit from the inverter (current of the motor
– see name plate).
In the presence of a low network voltage the current set must take into
consideration a margin (eg. 15%) which compensates for the low voltage.
RO >
DIRECTION OF
ROTATION OF THE
MOTOR
(only models with a
three-phase outlet)
ONLY PRESENT FOR A THREE-PHASE OUTLET - Sets the direction of rotation of the
three-phase motor (clockwise or anti-clockwise)
Содержание TISSEL-100
Страница 2: ......
Страница 77: ...77 30 5 TISSEL 100 TISSEL 100 OFF ON...
Страница 80: ...80 30 TISSEL 100 TISSEL 100 10 Qmax 80 V 80 x 10 8 70 Pset 4 4 x 70 2 8 TISSEL 100 230 50...
Страница 83: ...83 BASIC P 2P A RO ADV d MF LF HF Td PF TPF TP TF RF FS US EI i...
Страница 84: ...84 EO AI AT W V Pd iDRY FM FLAT SET F INSP WH TH NS SH E1 E1H E2 E2H E3 E3H E4 E4H EE TEST...
Страница 92: ...92 OVERTEMP MODULE COM ERROR LOW LEVEL EXT OFF 2 Prestazioni della pompa inferiori a quelle di targa...
Страница 94: ......
Страница 95: ......