TECHNICAL DATA
• Supply voltage: 230+/-10% V single phase
• Outlet voltage: 230 V three-phase
• Frequency: 50-60 Hz
• Level of protection: IP 65
• Vertical work position, with entrance of liquid from below and exit from above.
ATTENTION: in the presence of a low voltage (nominal value -10%) there may be power surges at the start and at
maximum power
POWER AND ABSORPTIONS
Model
V in
V out
A out
Fuse (A)
P2 max (kW)
P2 max (HP)
TISSEL-100 (7 A)
1 ~ 230 V
3 ~ 230 V
7
20 (6x32)
1.1
1.5
TISSEL-100 (12 A) 1 ~ 230 V
3 ~ 230 V
12
25 (6x32)
2.2
3.0
SELF-LIMITATION DUE TO OVERLOAD
If the current recorded by the inverter or the temperature of the components of the inverter exceed the safety limits TISSEL-100
starts a progressive reduction in the frequency of operation until the values exceeding the limits return to normal.
ILLUMINATED SIGNS
ON
OFF
FLASHING
TISSEL-100 does not detect a power supply.
ATTENTION: the absence of a power supply is not guaranteed, the card could
be damaged but still live.
TISSEL-100 is live but the pump is not running (STAND-BY)
TISSEL-100 is live and the pump is running
TISSEL-100 is live but OUT OF SERVICE (or in TEST), restoration is only manual
TISSEL-100 is in a state of alarm, restoration is only manual
Содержание TISSEL-100
Страница 2: ......
Страница 77: ...77 30 5 TISSEL 100 TISSEL 100 OFF ON...
Страница 80: ...80 30 TISSEL 100 TISSEL 100 10 Qmax 80 V 80 x 10 8 70 Pset 4 4 x 70 2 8 TISSEL 100 230 50...
Страница 83: ...83 BASIC P 2P A RO ADV d MF LF HF Td PF TPF TP TF RF FS US EI i...
Страница 84: ...84 EO AI AT W V Pd iDRY FM FLAT SET F INSP WH TH NS SH E1 E1H E2 E2H E3 E3H E4 E4H EE TEST...
Страница 92: ...92 OVERTEMP MODULE COM ERROR LOW LEVEL EXT OFF 2 Prestazioni della pompa inferiori a quelle di targa...
Страница 94: ......
Страница 95: ......