System Setup: Operation
Ctrl Nr: PM375118-004
59
9.2.1
Switch Default Settings
Switching
– Fast Settings
Parameter
Value
High Limit
120%
Low Limit
80%
Delay
0 Samples
Ratchet
2%
Switching
– Slow Settings
Parameter
Value
High Limit
110%
Low Limit
90%
Delay
256
Samples
Ratchet
0
Switching
– Selectors
Switch
Value
Mode
VSS
Retransfer
Yes
Switching
– Retransfer
Parameter
Value
Delay
10 Seconds