WaveStar Static Transfer Switch 2000A 3-Pole
82
Ctrl Nr: PM375118-004
13.4
SAS Board Transfers
If the Monitor fails to transfer the load, the SAS board will take over the transfer. If Alarms appear
showing the SAS board in control, follow these steps:
1. Check the
Alarms
page for alarms showing the SAS board is in control.
2. Login on the
Home
page as Administrator or other higher level authorization.
3. Touch the
Reset
button on the
Alarms
page to clear alarms. (Alarms will remain listed in the
Event Log.)
4. Check that SAS board alarms clear and do not reappear.
5. If SAS board alarms reappear, contact PDI Service at +1.800.225.4838.
13.5
Component Failure
The STS has substantial component redundancy and a single component failure will normally not impact
operation. Nevertheless, if alarms indicate component failure, call PDI Service at +1.800.225.4838.
Содержание WaveStar 2000A
Страница 1: ...WaveStar Static Transfer Switch 2000A 3 Pole Installation and Operation Ctrl Nr DOC15139 Revision 004 ...
Страница 13: ...System Description Ctrl Nr PM375118 004 13 Figure 5 STS 2000A 3 Pole One line Diagram ...
Страница 25: ...Installation Planning Ctrl Nr PM375118 004 25 Figure 9 General Assembly Drawing Customer Power Connections ...
Страница 66: ...WaveStar Static Transfer Switch 2000A 3 Pole 66 Ctrl Nr PM375118 004 Touch Reset to reset the modem ...
Страница 76: ...WaveStar Static Transfer Switch 2000A 3 Pole 76 Ctrl Nr PM375118 004 Figure 36 Help Procedure Examples ...